[Section]/Item
Value
Range
Description
Sector Count:
1 to 5
This parameter sets the number of sectors
contained in this controlled device. This
version of the application supports 1 to 5
sectors for each session.
Data Link Address:
0 to 65535
This parameter uniquely defines the data link
address for this unit on the communication
channel.
Failure Delay:
0 to 2000
This parameter sets the minimum number of
seconds to delay before polling this session
when it is not online. This parameter is only
used in unbalanced mode.
Confirm Timeout:
0 to
4,294,967,296
This parameter sets the number of
milliseconds to wait for a confirm response
from the controlled device.
Retry Count:
0 to 255
This parameter sets the number of retries to
be performed on the controlled device when
a communication error occurs.
C1/C2 Poll Count Pend:
0 to 100
This parameter sets the maximum number of
Class 1 and Class 2 polls performed on this
session before trying the next session. This
parameter prevents a session from
monopolizing the communication port.
Class 1 Polls:
0 to 65535
This parameter sets the maximum number of
class one polls performed on this session
before switching to another session. This
parameter prevents a session from
monopolizing the communication port.
Class 1 Pend Delay:
0 to
4,294,967,296
This parameter sets the minimum number of
milliseconds to delay between Class 1 polls
for pending data.
Class 2 Pend Delay:
0 to
4,294,967,296
This parameter sets the minimum number of
milliseconds to delay between Class 2 polls
for pending data.
Class 1 Poll Delay:
0 to
4,294,967,296
This parameter sets the minimum number of
milliseconds to delay between each Class 1
poll.
Class 2 Poll Delay:
0 to
4,294,967,296
This parameter sets the minimum number of
milliseconds to delay between each Class 2
poll.
Response Timeout:
0 to
4,294,967,296
This parameter sets the maximum number of
milliseconds to wait for a confirmation from
the controlled station to a request from this
module.
[Section]/Item
Value
Range
Description
[IEC-103 MASTER
SESSION x SECTOR y]
This section sets the parameters for a
specific sector of a session.