5.8.2 List of Cause of Transmission Codes
In Monitor Direction
COT
Description
1
spontaneous
2
cyclic
3
reset frame count bit (FCB)
4
reset communication unit (CU)
5
start/restart
6
power on
7
test mode
8
time synchronization
9
general interrogation
10
termination of general interrogation
11
local operation
12
remote operation
20
positive ack of command
21
negative ack of command
31
transmission of disturbance data
40
positive ack of generic write command
41
negative ack of generic write command
42
valid data response to generic read command
43
invalid data response to generic read command
44
generic write confirmation
In Control Direction
COT
Description
8
time synchronization
9
initiation of general interrogation
20
general command
31
transmission of disturbance data
40
generic write command
42
generic read command
5.8.3 List of Function Types
Fun
Description
Symbol
128
Distance protection
t(z)
160
Overcurrent protection
l>>
176
Transformer differential protection
l
T
192
Line differential protection
lL
254
Generic function type
GEN
255
Global function type
GLB