MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 116 of 152
ProSoft Technology, Inc.
February 22, 2013
The following table defines the contents of the Configuration Error (Cfg Err) word.
Each bit in the word corresponds to an error condition recognized when the
module is configured. There is a separate word for each application port. This
data is reported in the status data area previously defined.
Bit
Code
Description
0
0x0001
Invalid baud rate selected
1
0x0002
Invalid parity selected
2
0x0004
Received timeout set to 0
3
0x0008
Invalid Port selected for a session
4
0x0010
Invalid sector count for session
5
0x0020
Could not allocate memory for sector of a session.
6
0x0040
7
0x0080
Invalid failure delay or confirm timeout for session.
8
0x0100
9
0x0200
10
0x0400
11
0x0800
12
0x1000
13
0x2000
14
0x4000
15
0x8000
The following table lists all potential errors that can be generated by the IEC
60870-5-103 Master driver:
5.6.2 MVI56-IEC 60870-5-103 Master Communication Module Error
Codes
Error
Description
51
Physical layer error - Error transmitting message
52
Physical layer error - Intercharacter timeout occurred before message fully received.
53
Physical layer error - Frame not entirely received before timeout condition.
54
Physical layer error - Invalid frame length.
101
Link layer error - Invalid checksum received
102
Link layer error - Address unknown to module
103
Link layer error - Link established
104
Link layer error - Link failed
105
Link layer error - Received primary
106
Link layer error - FCB error discard
107
Link layer error - FCB error repeat
108
Link layer error - Invalid start character received
109
Link layer error - Invalid second character received
110
Link layer error - Invalid ending character received
111
Link layer error - Length mismatch error
112
Link layer error - Illegal function
113
Link layer error - No confirmation received