[Section]/Item
Value
Range
Description
Common ASDU Address:
0 to 255
This parameter sets the common ASDU
address to association with this sector of the
specified session. This parameter is usually
set the same as the Data Link Address
when only one sector is utilized.
Online Time Sync:
Yes or No This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command when the unit is
first recognized as being online. This should
only be utilized for devices that do not send
an EOI message after initializing.
Online General Int:
Yes or No This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command when the unit is first
recognized as being online. This should only
be utilized for devices that do not send an
EOI message after initializing.
EOI Time Sync:
Yes or No This parameter specifies if the sector in the
controlled device will be sent a time
synchronization command after this module
received an EOI message from the
controlled unit.
EOI General Int:
Y or N
This parameter specifies if the sector in the
controlled device will be sent a general
interrogation command after this module
received an EOI message from the
controlled unit.