ProSoft Technology MVI56-103M User Manual
Page 128

Reference
MVI56-103M ♦ ControlLogix Platform
User Manual
IEC 60870-5-103 Master Communication Module
Page 128 of 152
ProSoft Technology, Inc.
February 22, 2013
General commands
Inf Description
Com
Typ
e
Fun
128
160
176
192
254
255
t(z)
l>>
l
T
l
L
GEN GLB
16 auto-recloser on/off
On/Off 20
X
X
X
17 teleprotection on/off
On/Off 20
X
X
18 protection on/off
On/Off 20
X
X
X
X
19 LED reset
On
20
X
X
X
X
23 activate characteristic 1
On
20
X
24 activate characteristic 2
On
20
X
25 activate characteristic 3
On
20
X
26 activate characteristic 4
On
20
X
Generic functions
Inf
Description
Type Fun
128
160
176
192
254
255
t(z)
l>>
l
T
l
L
GEN GLB
240 read headings of all defined groups
21
X
241 read values or attributes of all entries
of one group
21
X
243 read directory of a single entry
21
X
244 read value or attribute of a single entry
21
X
245 general interrogation of generic data
21
X
248 write entry
10
X
249 write entry with confirmation
10
X
250 write entry with execution
10
X
251 write entry abort
10
X
5.8.6 Definition and Presentation of ASDUs In Monitor Direction
TYPE 1: Time-tagged
Bytes
Description
Spec
1
Value of 1
1
0x81
1
COT
1
Common address of ASDU
1
Function Type
1
Information number
1
DPI (0 to 3)
7.2.6.5
4
4-octet binary time
7.2.6.28
1
SIN
7.2.6.23