Iec-870-5-103 master port x – ProSoft Technology MVI56-103M User Manual
Page 37

MVI56-103M ♦ ControlLogix Platform
Configuring the MVI56-103M Module
IEC 60870-5-103 Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 37 of 152
February 22, 2013
2.5
[IEC-870-5-103 Master Port x]
These section configures the communication parameters for each application
serial port on the module. The following illustration shows typical settings for a
Master port.
[IEC-870-5-103 Master Port 0]
Baud Rate : 19200
Parity : Even
RTS On : 0
RTS Off : 1
Minimum Delay : 10
Receive Timeout : 2000
Single char ACK F0,1 or 3 : Yes
2.5.1 Baud Rate
This is the baud rate to be used on the port. Enter the baud rate as a value. For
example, to select 19K baud, enter 19200.
Baud Rate
Parameter Value Options
110
110
150
150
300
300
600
600
1200
12 or 1200
2400
24 or 2400
4800
48 or 4800
9600
96 or 9600
19,200
19, 192 or 19200
38,400
38, 384 or 38400
57,600
57 or 576
115,200
115 or 1152
2.5.2 Parity
N, O, E, M, or S
This parameter sets the parity to be used on the port. The values correspond to
the following settings: N=None, O=Odd, E=Even, M=Mark and S=Space.
Note: The 103M specification supports only Even Parity.
2.5.3 RTS On
0 to 65535
milliseconds
This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.