Instructions: Follow the procedure outlined above; put the appropriate information into the following test form.
Make certain to include information about the building location, and the type of fan/gauge used (on the front
page).
The test form is laid out in the same fashion as Retrotec’s FanTestic software program. Once this form is
completed, the information can be entered into FanTestic to provide the results of: Air flow at STP in CFM at 50
Pa, Air change rate per hour at 50 Pa, Flow/unit floor area in CFM/sqft at 50 Pa, Flow/unit enclosure area in
CFM/sqft at 50 Pa, Equivalent Leakage Area in sqin at 10 Pa, and LBL Effective Leakage Area in sq in at 4 Pa. These
results can be recorded on this test form in order to keep a paper record of this test.
Test Date:
Test Time:
Test Set:
Pressurize
Depressurize
Wind speed:
mph
Wind direction:
Temperature, initial (˚F):
Indoor
Outdoor
Height x Temperature difference:
(Indoor – Outdoor) x height of building
ft˚F
Bias Pressure, initial
[Pa]:
Time per Bias Pressure:
s
Building pressure [Pa]:
Blower Door pressure
[Pa]:
Range Plate:
Time per Building Pressure:
s
Bias Pressure, final [Pa]:
Temperature, final (˚F):
Indoor
Outdoor
Results
Value
Units
Error (%)
Air flow at STP
CFM at 50 Pa
Air change rate
/h at 50 Pa
Flow / unit floor area
CFM/sqft at 50 Pa
Flow / unit enclosure area
CFM/sqft at 50 Pa
Equivalent Leakage Area
sq in at 10 Pa
LBL Effective Leakage Area
sq in at 4 Pa
Building Air Leakage Test Recording Form – ASTM E779-10