Air tightness requirements for assemblies – Retrotec Residential Pressure & Air Leakage User Manual
Page 60
Page 60 of 75
©Retrotec Inc. 2014
Air Tightness Requirements for Assemblies
Table 17: Air tightness requirements for Assemblies
Standard
Region
Comments
Requirement
ACH50
n
50
CFM
75
/sq ft
(m
3
/hr)
50
/m
2
North America
Canadian NBC for RH
Canada
0.1
(L/s 50)/m
2
0.26
0.02
0.28
National Canadian Building
Code
Canada
Assemblies
0.15
(L/s 50)/m
2
0.33
0.025
0.35
Comparison of different Air Leakage Results for the same enclosure
Table 18: Comparison of different units for a house 50 x 30 x 20 feet, with n=0.65; proposed units are highlighted
Result
Units
Application
1,191
CFM50
House leakage in the US
1,550
CFM75
Large building leakage in the US
0.397
CFM50/sq ft
House and duct leakage in the US
0.253
CFM50/sq ft
House and duct leakage in the US, MLR
0.192
CFM50/sq ft
House and duct leakage in the US
0.250
CFM75/sq ft
Large building leakage in the US
0.249
(CFM @ 0.3 in WC)/sq ft
Large building leakage in the US
66
sq in EfLA4
House leakage in the US
1.06
sq in EfLA4/100 sq ft
Environmental Tobacco Smoke - apartment leakage in the US
123
sq in EqLA10
House leakage in Canada and US
157
sq in EqLA50
1.98
sq in EqLA10/100 sq ft
2.53
sq in EqLA50/100 sq ft
2.38
ACH50, n
50
Proposed for houses and large buildings worldwide
0.000107
SLA, sq in EfLA50/ sq in
House leakage in WA state must be 0.00030 or less
107
EfLA50/10
6
sq in
175
EqLA50/10
6
sq in (surface area)
Proposed for all buildings
0.56
Q50, m
3
/s
Large building leakage in Europe
196
V
4 ,
m
3
/h
All building leakage in France
2,023
V
50 ,
m
3
/h
Large building leakage in Europe