beautypg.com

๐‘‡๐‘œ๐‘ก๐‘Ž๐‘™ ๐ด๐‘–๐‘Ÿ ๐ป๐‘Ž๐‘›๐‘‘๐‘™๐‘’๐‘Ÿ ๐น๐‘™๐‘œ๐‘ค, Can be calculated directly or read from table 10, ๐‘ต๐‘บ๐‘ถ๐‘ท ๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท โˆš ๐‘ต๐‘บ๐‘ถ๐‘ท ๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท โ€“ Retrotec Residential Pressure & Air Leakage User Manual

Page 48

background image

Page 48 of 75
ยฉRetrotec Inc. 2014

Correct Total Air Handler Flow reading to what it would be if the standard filter was in place instead of
the TrueFlowยฎ

The flow reading on Channel B is the Total Air Handler Flow. In order to determine the actual flow, as it would
be with a standard filter in place, the Adjusted Total Air Handler Flow needs to be calculated from the Normal
System Operating Pressure (NSOP) and the TrueFlowยฎ System Operating Pressure (TFSOP).

The easy way

With a Retrotec gauge, first set n to 0.5 using the Set Up key. Then measure the supply pressure in a stable
location under normal conditions with a clean filter. Letโ€™s say its 121 Pa. Set Pressure on the gauge to 121 Pa
and Enter even though we arenโ€™t going to use the gauge to control anything, this step makes the calculation that
comes next, easy. With the Flow Grid installed and Gauge set to the Flow Grid, measure the flow at say 1000
CFM on Channel B with a pressure of 100 Pa on Channel A. To get the gauge to perform the correction, press the
[@] key until the previous supply plenum pressure appears, such as โ€œ1100 CFM @121 Paโ€ for this example. The
flow is now corrected without any further calculations.

To confirm this calculation is correct you can set NSOP to 121 and TFSOP to 100 in the below equation. Now, do
it the easy way.

The hard way:

The Adjusted Total Air Handler Flow = โˆš

NSOP

TFSOP

ร— ๐‘‡๐‘œ๐‘ก๐‘Ž๐‘™ ๐ด๐‘–๐‘Ÿ ๐ป๐‘Ž๐‘›๐‘‘๐‘™๐‘’๐‘Ÿ ๐น๐‘™๐‘œ๐‘ค

Eg: A total air handler flow of 1000 CFM is measured, the NSOP=75 Pa and the TFSOP =60Pa. Calculate 75/60= 1.25. Square root of 1.25 = 1.118

Multiply air handler flow of 1000 CFM by 1.118 to get an Adjusted Total Air Handler Flow of 1,118 CFM which represents the actual
system air handler flow.

โˆš

NSOP

TFSOP

can be calculated directly or read from Table 10.

Table 10: Square roots of Normal to TrueFlowยฎ System Operating Pressure ratios.

๐‘ต๐‘บ๐‘ถ๐‘ท

๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท

โˆš

๐‘ต๐‘บ๐‘ถ๐‘ท

๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท

๐‘ต๐‘บ๐‘ถ๐‘ท

๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท

โˆš

๐‘ต๐‘บ๐‘ถ๐‘ท

๐‘ป๐‘ญ๐‘บ๐‘ถ๐‘ท

1.40

1.183

1.05

1.025

1.39

1.179

1.04

1.020

1.38

1.175

1.03

1.015

1.37

1.170

1.02

1.010

1.36

1.166

1.01

1.005

1.35

1.162

1.00

1.000

1.34

1.158

0.99

0.995

1.33

1.153

0.98

0.990

1.32

1.149

0.97

0.985

1.31

1.145

0.96

0.980

1.30

1.140

0.95

0.975

1.29

1.136

0.94

0.970

1.28

1.131

0.93

0.964

1.27

1.127

0.92

0.959

1.26

1.122

0.91

0.954

1.25

1.118

0.90

0.949

1.24

1.114

0.89

0.943

1.23

1.109

0.88

0.938

1.22

1.105

0.87

0.933

1.21

1.100

0.86

0.927

1.20

1.095

0.85

0.922

1.19

1.091

0.84

0.917

1.18

1.086

0.83

0.911

1.17

1.082

0.82

0.906

1.16

1.077

0.81

0.900

1.15

1.072

0.80

0.894