Exiting programming mode – RISCO Group LightSYS Ver 2.xx User Manual
Page 20

Available Options per Keypad Type:
Wired keypad :
•
Label: provide a meaningful name (see page xx for details)
•
Partition assignment: (in most cases this is left as 1)
•
Masking : enables user / keypad authorization granularity per partition
•
Controls: enables emergency, multi-view
Slim 2-way Wireless keypad:
•
Label: provide a meaningful name (see page xx for details)
•
Partition assignment: (in most cases this is left as 1)
•
Masking : enables user / keypad authorization granularity per partition
•
Controls: enables emergency, exit beeps
•
Serial Number
•
Function Key > panic , MS Listen-talk, Disable
•
UO 1 – 3
1-Way Wireless keypad :
•
Label: provide a meaningful name (see page xx for details)
•
Partition assignment: (in most cases this is left as 1)
•
Masking : enables user / keypad authorization granularity per partition
•
Controls: enables emergency
•
Serial Number
Exiting Programming Mode
1. Set SW1 – 2 (Default) to OFF position.
2. Close the main box in order to prevent Front Tamper Alarm.
3. Press [*] repeatedly to return to ‘Main Menu’.
4. Press
>
to Exit and SAVE your settings.
Note:
The system will not allow exit from the Installer mode if a ‘Tamper’ or ‘System Fault’
condition exists. Correct any tamper and/or system fault conditions before attempting to exit
the Installer mode.
20
LightSYS Quick Installer Guide