Anomalies related to the plumbing circuit – MCZ Club HYDRO 15 kW User Manual
Page 40

PELLET STOVES
Chapter 6
INSTALLATION AND USE MANUAL
page
40
Problems / Causes / Solutions
Technical service - Rights reserved MCZ GROUP S.p.A. - Reproduction prohibited
PROBLEM
POSSIBLE CAUSES
REMEDY
In
the
automatic
position
the
stove
always runs at full
power.
1. Room thermostat set to maximum.
2. Temperature sensor defective.
3. Control panel defective or broken.
1. Reset the thermostat temperature.
2. Check the operation of the sensor
and replace if necessary.
3. Check the panel and replace if
necessary.
The stove does not run 1. Lack of electricity supply.
2. Pellet sensor in lockout.
3. Fuse blown.
1. Check that the electric socket is plugged
in and that the main switch is in position
“I”.
2. Clear lockout by resetting the rear
thermostat, replace the thermostat if
it happens again.
3. Replace the fuse.
ANOMALIES RELATED TO THE PLUMBING CIRCUIT
PROBLEM
POSSIBLE CAUSES
REMEDY
No
increase
in
temperature
with
stove in operation
1. Incorrect combustion adjustment.
2. Boiler / system dirty.
3. Insufficient stove power.
4. Poor pellet quality
1. Check recipe and parameters.
2. Check and clean the boiler.
3. Check that the stove is properly
sized for the requirements of the
system.
4. Use MCZ pellets
Condensation
in
boiler
1. Incorrect temperature setting.
2. Insufficient fuel consumption.
1.
Set the stove to a higher
temperature.
2.
Check the recipe and/or technical
parameters.
Radiators
cold
in
winter
1. Room thermostat (local or remote)
set too low. If remote thermostat,
check if it is defective.
2. Circulator does not run because
blocked.
3. Circulator does not run.
4. Radiators have air in them
1.
Set to higher temperature or
replace. (if remote)
2.
Free up the circulator by removing
the plug and turning the shaft with a
screwdriver.
3.
Check the electrical connections of
the circulator; replace if necessary.
4.
Vent the radiators
Hot water is not
provided
1. Circulator (pump) blocked
1.
Free the circulator (pump)
ATTENTION!
The operations
in italics
must be carried out by
specialised MCZ personnel.
The manufacturer refuses to accept any responsibility
and the guarantee lapses if this condition is not
respected.
- Club HYDRO 15 kW High Efficiency Club HYDRO 15 kW Ver.2009 cod. 7109007 Club HYDRO 22 kW Club HYDRO 22 kW High Efficiency Ego HYDRO Ego HYDRO High Efficieny Musa HYDRO 15 kW Musa HYDRO 15 kW Ver.2009 cod. 7109008 Musa HYDRO 15 kW High Efficiency Musa HYDRO 22 kW Musa HYDRO 22 kW High Efficiency Star HYDRO Star HYDRO High Efficieny Suite HYDRO 15 kW Suite HYDRO 15 kW High Efficiency Suite HYDRO 15 kW Ver. 2009 cod. 7109007 Suite HYDRO 22 kW Suite HYDRO 22 kW High Efficiency