13 Troubleshooting

68

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

Related Parameters

Table 35 Parameters related to bUS Error Auto-Reset Functionality

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in

Table 36

.

Table 36 Option Fault Monitor Descriptions

Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:

• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3/V status. U6-99 is cleared upon a network-issued fault reset and upon

power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.

No.

(Addr. Hex)

<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and proper safety measures, when installing

an emergency stop switch.

<5> Available in drive software versions PRG:1024 and later when combined with option firmware version VST800251 and later. Not available in

drive software versions PRG:508.

Name

Description

Default

F6-01

(03A2)

Operation Selection after
Communications Error

Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<5>

5: Alarm Ramp to Stop

<5>

<6> Available in option firmware version VST800251 and later.

1

F6-14

<6>

(03BB)

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-16

<6>

(03F4)

Communication Loss Timeout

Sets the timeout value for communication loss detection in tenths of
a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Note: A change to this parameter setting is not effective until main
power to the drive is cycled.

0.0

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault state.

Network Link Down

BUS ERROR

1300

No network link to option board.

Network Failure

BUS ERROR

1301

Connection with PLC Timeout.

Default MAC Address

None

1303

Factory default MAC Address programmed into the option. Return for
reprogramming.

No IP Address

None

1304

No IP Address has been programmed into the option.

No Station Name

None

1305

No Station Name has been programmed into the option.

Config Error

None

1306

Configuration error on power-up.

Init. Failure

None

1307

Initialize error on power-up.

Permanent
Communication Loss

BUS ERROR

1308

Fatal error in MAC/PHY hardware, requires power cycle to recover.