9 Option Drive Parameters

34

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

F7-14

Duplex Mode Selection

Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half (port 1)/Auto (port 2)

<5>

4: Half (port 1)/Full (port 2)

<5>

5: Auto (port 1)/Half (port 2)

<5>

6: Auto (port 1)/Full (port 2)

<5>

7: Full (port 1)/Half (port 2)

<1>

8: Full (port 1)/Auto (port 2)

<5>

1

<4>

F7-15

Communication Speed Selection

Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
101: 10 (port 1)/100 Mbps (port 2)

<5>

102: 100 (port 1)/10 Mbps (port 2)

<5>

10

F7-16

<6>

Communication Loss Timeout

Sets the timeout value for communication loss detection in tenths of
a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.

0.0

F7-23 to F7-27

Option Firmware Version VST800250
Dynamic Output Assembly
Parameters

Configurable outputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to F7-27 and
F7-33 to F7-37 by the drive, that value will take precedent over a
value set by the configuration software. If the value in the drive is 0
(default), the value from the configuration software will be used.

0

Option Firmware Version VST800251
Dynamic Output Assembly
Parameters

Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration software,
those values will be used, otherwise, the values of the drive
parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will
be used.

F7-33 to F7-37

Option Firmware Version VST800250
Dynamic Input Assembly
Parameters

Configurable inputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to F7-27 and
F7-33 to F7-37 by the drive, that value will take precedent over a
value set by the configuration software. If the value in the drive is 0
(default), the value from the configuration software will be used.

0

Option Firmware Version VST800251
Dynamic Input Assembly
Parameters

Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration software,
those values will be used, otherwise, the values of the drive
parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will
be used.

H5-11

Communications ENTER Function
Selection

Select the function for the ENTER command that saves parameter
data to the drive.
0: Parameter changes are activated when ENTER command is
written
1: Parameter changes are activated immediately without use of
ENTER command

1

<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency reference

via the master device, set b1-01 to 3.

<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper safety measures, such as

installing an emergency stop switch.

<3> Drive software versions 1012 and later have F6-07 and F6-08 both set to 1.

<4> Drive software versions 1014 and earlier have F7-14 default of 0.

<5> Available in drive software versions PRG:1024 and later when combined with option firmware version VST800251 and later. Not available in

drive software versions PRG:508.

<6> Available in option firmware version VST800251 and later.

No.

Name

Description

Default