9 Option Drive Parameters
34
YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual
F7-14
Duplex Mode Selection
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half (port 1)/Auto (port 2)
4: Half (port 1)/Full (port 2)
5: Auto (port 1)/Half (port 2)
6: Auto (port 1)/Full (port 2)
7: Full (port 1)/Half (port 2)
8: Full (port 1)/Auto (port 2)
F7-15
Communication Speed Selection
Sets the communication speed.
10: 10 Mbps
100: 100 Mbps
101: 10 (port 1)/100 Mbps (port 2)
102: 100 (port 1)/10 Mbps (port 2)
10
F7-16
Communication Loss Timeout
Sets the timeout value for communication loss detection in tenths of
a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
0.0
F7-23 to F7-27
Option Firmware Version VST800250
Dynamic Output Assembly
Parameters
Configurable outputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to F7-27 and
F7-33 to F7-37 by the drive, that value will take precedent over a
value set by the configuration software. If the value in the drive is 0
(default), the value from the configuration software will be used.
0
Option Firmware Version VST800251
Dynamic Output Assembly
Parameters
Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration software,
those values will be used, otherwise, the values of the drive
parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will
be used.
F7-33 to F7-37
Option Firmware Version VST800250
Dynamic Input Assembly
Parameters
Configurable inputs 1 to 5.
If a value other than 0 is assigned to parameters F7-23 to F7-27 and
F7-33 to F7-37 by the drive, that value will take precedent over a
value set by the configuration software. If the value in the drive is 0
(default), the value from the configuration software will be used.
0
Option Firmware Version VST800251
Dynamic Input Assembly
Parameters
Configurable outputs 1 to 5.
If a value other than 0 is assigned in the configuration software,
those values will be used, otherwise, the values of the drive
parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will
be used.
H5-11
Communications ENTER Function
Selection
Select the function for the ENTER command that saves parameter
data to the drive.
0: Parameter changes are activated when ENTER command is
written
1: Parameter changes are activated immediately without use of
ENTER command
1
<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency reference
via the master device, set b1-01 to 3.
<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper safety measures, such as
installing an emergency stop switch.
<3> Drive software versions 1012 and later have F6-07 and F6-08 both set to 1.
<4> Drive software versions 1014 and earlier have F7-14 default of 0.
<5> Available in drive software versions PRG:1024 and later when combined with option firmware version VST800251 and later. Not available in
drive software versions PRG:508.
<6> Available in option firmware version VST800251 and later.
No.
Name
Description
Default