10 PROFINET Messaging

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

37

Table 13 PROFIdrive Compatible Status Word for the PROFIdrive Communication Profile

Bit

Name

Value

STATE/Description

0 RDY_ON

1

READY TO SWITCH ON.

0

NOT READY TO SWITCH ON.

1 RDY_RUN

1 READY

TO

OPERATE.

0 OFF1

ACTIVE.

2 RDY_REF

1 ENABLE

OPERATION.

0 DISABLE

OPERATION.

3 TRIPPED

1 FAULT.
0 No

fault.

4 OFF_2_STA

1 OFF2

inactive.

0 OFF2

ACTIVE.

5 OFF_3_STA

1 OFF3

inactive.

0 OFF3

ACTIVE.

6 SWC_ON_INHIB

1

SWITCH-ON INHIBIT ACTIVE.

0

SWITCH-ON INHIBIT NOT ACTIVE.

7 ALARM

1 Warning/Alarm.
0 No

Warning/Alarm.

8

AT_SETPOINT

1

OPERATING. Actual value equals reference value (i.e., is within tolerance limits).

0

Actual value differs from reference value (i.e., is outside tolerance limits).

9 REMOTE

1

Drive control location: REMOTE.

0

Drive control location: LOCAL.

10 ABOVE_LIMIT

-

Not

supported.

11 to 15

-

-

Reserved