6 Procedure A

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

23

16.

Connect the ground wire at the option ground terminal FE. Tighten the screw to 0.5 ~ 0.6 Nm or (4.4 ~ 5.3 in lbs)
using an M3 Phillips screwdriver.

Figure 23

Figure 23 Connect the Ground Wire to the Option

17.

To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair Cat5e cable(s) into the
modular connector ports.

Refer to Network Topology and Connections on page 32

.

NOTICE: Do not connect or disconnect the communication cable while the drive is powered up or while the drive is in operation. Failure

to comply may cause a static discharge, which will cause the option card to stop working properly. Cycle power on the drive and option

card to attempt to reestablish functionality.

Figure 24

Figure 24 CN1 RJ45 CAT5e Communication Cable Ports

Option ground
terminal FE

Ground wire to
drive ground terminal
screw

RJ45 8-pin Shielded Twisted Pair
Cat5e cable(s)