YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

Parameter Data Transfer Examples

The following example shows how parameter data is transferred using the acyclic parameter access mechanism's READ
and WRITE.

Example 1: Reading a drive parameter

To read a Yaskawa Drive parameter, use the PNU of 1 and the actual address of the parameter in the SubIndex.

Write Request (Read Parameter Value)

Positive Read Response to Read Request

PROFIdrive compatible Parameter Channel

0x65 Vendor-specific

error Vendor-specific

error

0x66

Request not supported

Request not supported

0x67 Communication

error

Request cannot be completed because of communication error

0x6F Time-out

error

Request

aborted due to time-out

0x78 PZD

map

failure

Parameter

cannot be mapped to PZD (size mismatch or non-existent)

0x79

PZD memory failure

Parameter cannot be mapped to PZD (out of memory)

0x7A

Multiple PZD map

Parameter cannot be mapped to PZD (multiple PZD write)

0x8C

Set torque mode error

Cannot change mode to TORQUE (frequency is used)

0x90

Illegal Request ID

The request ID of the response is illegal

Error #

Meaning

Used at