beautypg.com

Yaskawa V1000-Series Option SI-EP3/V PROFINET User Manual

Page 19

background image

6 Procedure A

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

19

8.

Loosen the screws attaching the NEMA Type 1 conduit bracket to the drive to remove the NEMA Type 1 conduit
bracket.

Figure 14

Figure 14 Remove the NEMA Type 1 Conduit Bracket

9.

Select one of the four different length ground wires packaged with the option,

Figure 15

. Choose the proper

ground wire by first removing the ground terminal screw from the drive

Figure 16

. Test fit the screw (size M3.5 to

M6) into each of the four ground drive-side ring lugs prior to installation. Ground wire selection varies by drive
model.

Figure 15

Figure 15 Ground Wire Selection

10.

On IP20/NEMA Type 1 enclosure drives, the screw for the drive ground terminal also acts as one of the screws
that attaches the NEMA Type 1 conduit bracket to the drive. Reattach the NEMA Type 1 conduit bracket
according to

Figure 16

and connect the drive-side of the ground wire to the drive ground terminal.

Figure 16

Figure 16 Reattach the NEMA Type 1 Conduit Bracket and Connect the Ground Wire

To Option ground screw FE
Screw size: M3

To drive ground terminal
Screw size: M3.5 to M6

Ground terminal

Ground wire

Drive ground terminal/
located on NEMA Type 1
conduit bracket screw

Ground wire

Drive-side
ground terminal
ring lug
(size varies):
M3.5 to M6

Ring lug for
Option ground
FE
Size: M3