9 Option Drive Parameters
YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual
33
9
Option Drive Parameters
Before starting network communications, verify proper setting of drive parameters in
using the drive digital
operator.
Table 10 Parameter Settings
No.
Name
Description
Default
b1-01
Frequency Reference Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
(Set to 3 for
PROFINET)
b1-02
Run Command Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
1
(Set to 3 for
PROFINET)
F6-01
Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm (d1-04)
5: Alarm Ramp to Stop
1
F6-02
External Fault Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
0
F6-03
Stopping Method for External Fault
from Communication Option Board
Determines drive response for external fault input (EF0) detection
during communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-07
NetRef/ComRef Selection Function
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
1
F6-08
Reset Communication Related
Parameters
Determines if communication-related parameters F6- and F7-
are set back to original default values when the drive is
initialized using parameter A1-03.
0: Do not reset F6- and F7- parameters
1: Reset F6- and F7- parameters
Note: Setting this parameter does not affect communication-related
parameters.
0
bUS Error Auto Reset
0: Disabled
1: Enabled
0
F7-01 to F7-04
IP Address
Sets static IP address of the SI-EP3/V option when parameter F7-
13=0.
Note: Parameter F7-01 sets the most significant octet.
192 168 1 20
F7-05 to F7-08
Subnet Mask
Sets static Subnet Mask of network connection.
Note: Parameter F7-05 sets the most significant octet
255 255 255 0
F7-09 to F7-12
Gateway Address
Sets static Gateway address of network connection.
Note: Parameter F7-09 sets the most significant octet.
192 168 1 1
F7-13
Address Mode at Startup
Selects how the option address is set.
0: Static
2: DCP
2