Motion Control

Date: 08/18/04, Rev: 04-08

Page 10 of 22

TM.G5SW.020





P1-03 Distance Selection

Controls where the distance command come from

Setting Function

Description

0

Multi-Profile

Distance comes from the A2 parameters. See the command chart.

1

32 Bit Distance

Distance comes from Modbus addresses 5a8 and 5a9. This is used when an
external computer is used to set the destination. See P3-09 and P3-10.

2

Analog Distance Distance in controlled by an analog input to the controller.







P1-04 Switch Type

Tells the controller the normal state of the home and over-travel limit switches.

Setting Function

Description

0 Both

NO

Both home and over-travel limit switches are open when the machine is in the
middle of the travel zone.

1

OT NO, Home NC

Over-travel limit switches are open when the machine is in the middle of the
travel zone. Home limit switch is closed when the machine is in the middle of the
travel zone.

2

OT NC, Home NO

Over-travel limit switches are closed when the machine is in the middle of the
travel zone. Home limit switch is open when the machine is in the middle of the
travel zone

3 Both

NC

Both home and over-travel limit switches are closed when the machine is in the
middle of the travel zone.


Setting Range:

0 to 2

Factory Default:

0

Modbus Address:

0582 Hex

Distance Select

Multi-Profile

Setting Range:

0 to 3

Factory Default:

0

Modbus Address:

0583 Hex

Switch Type

Both NO