Error messages

In case of an error, the Sunny Boy 700U generates the error code according to the
operating mode and the detected error.

Error Code

Description

Error Type

Bfr-Srr

Communication between micro-controllers is failing

Error

EarthCur-
Max-Bfr

BFR-earth current between PV+ and GND is out of tolera-
ble range

Error

EarthCur-
Max-Srr

SRR-earth current between PV+ and GND is out of tolera-
ble range

Error

EEPROM

Transition failure during reading or writing of data EE-
PROM, the data is not essential for safe operation - this fail-
ure does not effect performance.

Error

EEPROM p

Data EEPROM defective, device is set to permanent dis-
able due to the fact that the data loss affects important func-
tions of the inverter. Contact SMA.

Error

EeRestore

Internal failure

Error

Fac-Bfr
Fac-Srr

The AC grid frequency is exceeding the allowable range.
(„Bfr“ or „Srr“ is an internal message and is not important
to the user.) The Sunny Boy assumes that the public grid is
down and disconnects from the grid in order to avoid is-
landing.

Check the grid frequency and the grid cable connection in
the Sunny Boy enclosure. If the grid frequency is out of
range due to your local grid conditions contact the utility
company and ask, if it is permissable to change the grid
monitoring parameters of the inverter. Contact SMA about
how to change the grid monitoring parameters of your Sun-
ny Boy. If the grid frequency is within the tolerable range
and you still observe the failure message „Fac-Bfr“ or „Fac-
Srr“ contact SMA.

Disturbance

GFDI Fuse
Open

The GFDI-Fuse is defective or open

Error

Imax

Overcurrent on the AC side. This failure code is indicated
in case the current to the AC grid exceeds the specification.
This may happen in case of harmfull interference on the
grid. If you observe „F-Imax“ often, check your grid. For as-
sistance contact SMA.

Disturbance