9 Technical Data
Mounting Instructions
SCCP-JP-MA-Silence-en-10
31
9.3 Sunny Central 800CP-JP
Input (DC)
Output (AC)
Color of enclosure / door / base / roof
RAL 9016 / 9016 / 7004 / 7004
Configurable grid management functions
Power derating, reactive power setpoint,
dynamic grid support (e.g. LVRT)
Certificates and approvals (more available upon request)
EN 61000-6-2, EN 61000-6-4, CE conformity,
EEG EEG conformity, BDEW-MSRL / JETGR0002-1-2.0
(2011) / JETGR0003-1-2.0 (2011)* , Arrêté du 23/04/
08, R.D. 1663 / 2000, R.D. 661 / 2007
● Standard features
○ Optional features
— Not available
Type designation
SC 630CP-10-JP
* Type-tested by the manufacturer in accordance with JET (Japan Electrical Safety & Environment Technology Laboratories Foundation)
Max. DC power (at cos φ =1)
898 kW
Max. input voltage
1,000 V
MPP voltage range (50 Hz) / MPP voltage range (60 Hz)
583 V to 850 V* / 583 V to 850 V*
* At 1.05 V
AC, nom
cos phi = 1 and nominal power P
nom
DC voltage range (50 Hz) / DC voltage range (60 Hz)
530 V to 850 V / 530 V to 850 V
Rated input voltage
641 V
Max. input current
1,400 A
V
mpp min
at I
mpp
< I
DCmax
530 V (50 Hz) / 530 V (60 Hz)
Number of independent MPP inputs
1
Number of DC inputs
9
Rated power (at 25°C) / nominal AC power (at 50°C)*
* With mounted sound absorber
880 kVA 600 kVA
Nominal AC voltage / range
360 V / 324 V to 414 V
AC power frequency / range
50 Hz, 60 Hz / 47 Hz to 63 Hz
Rated power frequency / rated grid voltage
50 Hz / 315 V
Max. output current
1,411 A
Max. total harmonic distortion
< 3%
Power factor at rated power /
displacement power factor adjustable
1 / 0.9 lagging to 0.9 leading
Feed-in phases / connection phases
3 / 3