SMA SC 500CP-10-JP Mounting Instructions User Manual
Page 30

9 Technical Data
SMA Solar Technology AG
30
SCCP-JP-MA-Silence-en-10
Mounting Instructions
Protective Devices
General Data
Equipment
Input-side disconnection point
Motor-driven DC load-break switch
AC disconnect device
AC circuit breaker
DC overvoltage protection
Surge arrester type I
Lightning protection (according to IEC 62305-1)
Lightning protection level III
Grid monitoring
●
Islanding detection
active, passive
Ground fault monitoring / remote ground fault monitoring
○ / ○
Insulation monitoring
○
Surge arrester for communication interface/
string current monitoring
○ / ○
Surge arrester for auxiliary power supply
Surge arrester type I and type II
Protection class (according to IEC 62103) /
overvoltage category (according to IEC 60664-1)
I / III
Dimensions (width x height x depth)
2,562 mm / 2,272 mm / 1,210 mm
Weight*
* With mounted sound absorber
approx. 1,850 kg
Operating temperature range
-25°C to +62°C
Noise emission**
** Sound pressure level at a distance of 10 m with mounted sound absorber
55 dB(A)
Max. self-consumption (operation)*** /
self-consumption (night)
*** Self-consumption during rated operation
1,900 W / < 100 W
External auxiliary supply voltage
230 V / 400 V (3/N/PE)
Cooling concept
OptiCool
Degree of protection: electronics /
connection area (as per IEC 60529)
IP54 / IP43
Application
In unprotected outdoor environments
Maximum permissible value for relative humidity
(non-condensing)
15% to 95%
Maximum operating altitude above MSL
2,000 m
Fresh air consumption
3,000 m³/h
DC connection / AC connection
Ring terminal lug / ring terminal lug
Display
HMI touchscreen
Communication protocols
Ethernet (optical fiber optional), Modbus
Communication with Sunny String-Monitor
RS485