9  Technical Data

SMA Solar Technology AG

28

SCCP-JP-MA-Silence-en-10

Mounting Instructions

General Data

Equipment

Islanding detection

active, passive

Ground fault monitoring / remote ground fault monitoring

○ / ○

Insulation monitoring

Surge arrester for communication interface/

string current monitoring

○ / ○

Surge arrester for auxiliary power supply

Surge arrester type I and type II

Protection class (according to IEC 62103) /

overvoltage category (according to IEC 60664-1)

I / III

Dimensions (width x height x depth)

2,562 mm / 2,272 mm / 1,210 mm

Weight*

* With mounted sound absorber

approx. 1,850 kg

Operating temperature range

‒25°C to +62°C

Noise emission**

** Sound pressure level at a distance of 10 m with mounted sound absorber

53 db(A)

Max. self-consumption (operation)*** /

self-consumption (night)

*** Self-consumption during rated operation

1,900 W / < 100 W

External auxiliary supply voltage

230 V / 400 V (3/N/PE)

Cooling concept

OptiCool

Degree of protection: electronics /

connection area (as per IEC 60529)

IP54 / IP43

Application

In unprotected outdoor environments

Maximum permissible value for relative humidity

(non-condensing)

15% to 95%

Maximum operating altitude above MSL

2,000 m

Fresh air consumption

3,000 m³/h

DC connection / AC connection

Ring terminal lug / ring terminal lug

Display

HMI touchscreen

Communication protocols

Ethernet (optical fiber optional), Modbus

Communication with Sunny String-Monitor

RS485

Color of enclosure / door / base / roof

RAL 9016 / 9016 / 7004 / 7004

Configurable grid management functions

Power derating, reactive power setpoint, dynamic grid

support (e.g. LVRT)

Certificates and approvals (more available upon request)

EN 61000-6-2, EN 61000-6-4, CE conformity,

EEG EEG conformity, BDEW-MSRL / JETGR0002-1-2.0

(2011) / JETGR0003-1-2.0 (2011)* ,

Arrêté du 23/04/08, R.D. 1663 / 2000, R.D. 661 /

2007