9 technical data, 1 sunny central 500cp‑jp – SMA SC 500CP-10-JP Mounting Instructions User Manual
Page 27

SMA Solar Technology AG
9 Technical Data
Mounting Instructions
SCCP-JP-MA-Silence-en-10
27
9 Technical Data
9.1 Sunny Central 500CP‑JP
Input (DC)
Output (AC)
Efficiency*
Protective Devices
Max. DC power (at cos φ =1)
511 kW
Max. input voltage
600 V
MPP voltage range (50 Hz) / MPP voltage range (60 Hz)
332 V to 600 V* / 332 V to 600 V*
* At 1.05 V
AC, nom
cos phi = 1 and nominal power P
nom
DC voltage range (50 Hz) / DC voltage range (60 Hz)
311 V to 600 V / 321 V to 600 V
Rated input voltage
365 V
Max. input current
1,400 A
V
mpp min
at I
mpp
< I
DCmax
311 V (50 Hz) / 321 V (60 Hz)
Number of independent MPP inputs
1
Number of DC inputs
9
Rated power (at 25°C) / nominal AC power (at 50°C)*
* With mounted sound absorber
500 kVA
341 kVA
Nominal AC voltage / range
205 V / 185 V to 235 V
AC power frequency / range
50 Hz, 60 Hz / 47 Hz to 63 Hz
Rated power frequency / rated grid voltage
50 Hz / 205 V
Max. output current
1,411 A
Max. total harmonic distortion
< 3%
Power factor at rated power / displacement power factor
adjustable
1 / 0.9 lagging to 0.9 leading
Feed-in phases / connection phases
3 / 3
* Efficiency measured without internal power supply
Max. efficiency / European efficiency /
CEC weighted efficiency
98% / 97.7% / 97.4%
Input-side disconnection point
Motor-driven DC load-break switch
AC disconnect device
AC circuit breaker
DC overvoltage protection
Surge arrester type I
Lightning protection (according to IEC 62305-1)
Lightning protection level III
Grid monitoring
●