9  Technical Data

Mounting Instructions

SCCP-JP-MA-Silence-en-10

27

9 Technical Data

9.1 Sunny Central 500CP‑JP

Input (DC)

Output (AC)

Efficiency*

Protective Devices

Max. DC power (at cos φ =1)

511 kW

Max. input voltage

600 V

MPP voltage range (50 Hz) / MPP voltage range (60 Hz)

332 V to 600 V* / 332 V to 600 V*

* At 1.05 V

AC, nom

cos phi = 1 and nominal power P

nom

DC voltage range (50 Hz) / DC voltage range (60 Hz)

311 V to 600 V / 321 V to 600 V

Rated input voltage

365 V

Max. input current

1,400 A

V

mpp min

at I

mpp

< I

DCmax

311 V (50 Hz) / 321 V (60 Hz)

Number of independent MPP inputs

1

Number of DC inputs

9

Rated power (at 25°C) / nominal AC power (at 50°C)*

* With mounted sound absorber

500 kVA

341 kVA

Nominal AC voltage / range

205 V / 185 V to 235 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 205 V

Max. output current

1,411 A

Max. total harmonic distortion

< 3%

Power factor at rated power / displacement power factor

adjustable

1 / 0.9 lagging to 0.9 leading

Feed-in phases / connection phases

3 / 3

* Efficiency measured without internal power supply

Max. efficiency / European efficiency /

CEC weighted efficiency

98% / 97.7% / 97.4%

Input-side disconnection point

Motor-driven DC load-break switch

AC disconnect device

AC circuit breaker

DC overvoltage protection

Surge arrester type I

Lightning protection (according to IEC 62305-1)

Lightning protection level III

Grid monitoring