beautypg.com

H3C Technologies H3C S3600V2 Series Switches User Manual

Page 22

background image

16

If you do not have an OT terminal, follow callout B in

Figure 22

to make the connector: Peel the

insulation sheath by an appropriate length by using a wire stripper, and then bend the naked metal
part.

Step4

Connect the made connector to the grounding post of the grounding strip, and then fasten it with a hex
nut, as shown in

Figure 23

.

Figure 22 Make the grounding cable connector

Figure 23 Connect the grounding cable to a grounding strip

(1) Grounding post

(2) Grounding strip

(3) Grounding cable

(4) Hex nut

Grounding the switch with a grounding conductor buried in the
earth ground

If the installation site has no grounding strips, but earth ground is available, hammer a 0.5 m (1.64 ft) or
longer angle iron or steel tube into the earth ground to serve as a grounding conductor.

The angle iron must have a dimension no less than 50 × 50 × 5 mm (1.97 × 1.97 × 0.20 in) and the steel
tube must have a wall thickness no less than 3.5 mm (0.14 in) and be zinc-coated.

Weld the yellow-green grounding cable to the angel iron or steel tube and treat the joint for corrosion
protection.

This manual is related to the following products: