Stage 1: Freeze Protection
Step Two (2)
Press the
SET
Set
key again to access the Stage 1 set point.
The screen displays the current set point and the
S1
annunciator blinks on and off to indicate that the control is in
Set Point mode.
Then:
Press the
Up Arrow
key to increase the set point or the
Down Arrow
key to decrease the set point for the
evaporator freeze protection temperature you selected.
At 50ºF (10ºC) leaving water temperature, the setting should be
42ºF (6ºC).
Step Three (3)
Press the
SET
Set
key again to access Stage 1 differential.
The screen displays the current differential and the
DIF 1
enunciator blinks on and off to indicate that the control is in
Differential mode.
Then:
Press the
Up Arrow
key to increase the differential or the
Down Arrow
key to decrease the differential for the
setting you want.
The setting should be 12ºF (6ºC).
Step Four (4)
Press the
Set
key again to access Stage 1 cooling or
heating mode.
The screen displays the current mode;
C1
for cooling or
H1
for heating.