FSS Series Fountain Solution Systems
IAE-600
7-5 Graphic Panel Indicators and Switches
Compressor On Light (1.5 Ton Unit Only)
The
Compressor On
light turns on whenever the compressor is
operating.
Important!
Your AEC, Inc. warranty does not cover damage from evaporator freeze-up.
Be sure there is enough glycol in the system and that the High/Low thermostat
is set to the correct cutout temperature to prevent freeze-up!
Hot Gas By-Pass Light (1.5 Ton Unit Only)
The
Hot Gas By-Pass
light turns on when the hot gas bypass
valve is in operation. The
OUT1
LED
on the controller also lights
when the hot gas bypass valve is in operation.
Pump On Light
The
Pump On
light, installed on chillers with a pump, lights
whenever the pump(s) operates.
High Refrigerant Pressure Light (1.5 Ton Unit Only)
The
High Refrigerant Pressure
light comes on if the compressor
discharge pressure exceeds the limit of the high pressure cut-out
switch. The compressor stops but the pump(s) continue to run
until you manually reset the high pressure cut-out switch. Call a
qualified refrigeration service technician or contact the AEC
Service Department.
Low Refrigerant Pressure Light (1.5 Ton Unit Only)
The
Low Refrigerant Pressure
light comes on if the compressor
suction pressure drops below the limit of the low pressure cut-out
switch. The compressor shuts off, but the pump(s) continues to
run.
The indicator turns off and compressor restarts automatically when
the refrigerant pressure raises to the limit of the low pressure cut-
out switch. Call a qualified refrigeration service technician or
contact the AEC Service Department.