Technical specification – Super Systems 3L Series User Manual
Page 51
Series 3L Indicators
51
13. TECHNICAL SPECIFICATION
General
Temperature limits Operation: 0 to 55°C (32 to 131°F),
Storage: -10 to 70°C (14 to 158°F)
Humidity limits
Operation: RH: 5 to 90% non-condensing
Storage: RH: 5 to 90% non-condensing
Panel sealing
IP 65, Nema 4X
Shock
BS EN61010
Vibration
2g peak, 10 to 150Hz
Altitude
<2000 metres
Atmospheres
Not suitable for use above 2000m or in
explosive or corrosive atmospheres.
Electromagnetic
compatibility
(EMC)
BS EN61326
Electrical safety
BS EN61010 Installation cat. II; Pollution
degree 2
Installation
category II
The rated impulse voltage for equipment
on nominal 230V supply is 2500V
Pollution degree 2 Normally only non conductive pollution
occurs. Occasionally, however, a
temporary conductivity caused by
condensation shall be expected.
Physical
Series 3L
Panel mounting
1/4 DIN
Weight grams
420
Dimensions mm
96W x 96H x
90D
Panel cut-out
dimensions mm
92W x 92H
Operator interface
Type
LCD TN with backlight
Main PV display
Series 3L
4 digits
green
Lower display
5 character
starburst,
green
Status beacon
Units, outputs, alarms, active setpoint
Power requirements
Series 3L
100 to 240Vac, -15%, +10%
48 to 62Hz, max 8W
24Vac, -15%, +10%
24Vdc, -15%, +20%, +5% ripple voltage,
max 8W
Approvals
CE, cUL listed (file ES7766), Gost, FM,
EN14597TW approval number TW1222.
Transmitter PSU
Isolation
264Vac double insulated
Output Voltage
24Vdc, 20mA
Communications: serial communications option
Protocol
Modbus RTU slave
Modbus RTU Master broadcast (1
parameter)
Isolation
264Vac double insulated
Transmission
standard
EIA485 2-wire
Transmission
standard
EIA485 2-wire
Process Variable Input
Calibration accuracy <+0.25% of reading +1LSD
(1)
Sample rate
9Hz (110mS)
Isolation
264Vac double insulated from the PSU
and communications
Resolution (µV)
< 0.5µV with 1.6s filter (mV range)
< 0.25µV with 1.6s filter (Volts range)
Resolution (effective
bits)
>17 bits
Linearisation
accuracy
<0.1% of reading
Drift with
temperature
<50ppm (typical) <100ppm (worst case)
Common mode
rejection
48 - 62 Hz, >-120db
Series mode
rejection
48 - 62 Hz, >-93db
Input impedance
100M
Ω
(200KΩ on volts range C)
Cold junction
compensation
>30 to 1 rejection of ambient
temperature
External cold
junction
Reference of 0
O
C
Cold junction
accuracy
<+1
o
C at 25
o
C ambient
Linear (process)
input range
-10 to 80mV, 0 to 10V with external
potential divider module 100K
Ω/806Ω
Thermocouple Types K, J, N, R, S, B, L, T, C, custom
download
(2)
RTD Type
3-wire, Pt100 DIN43760
Bulb current
0.2mA
Lead compensation
No error for 22 ohms in all 3 leads
Input filter
Off to 100 seconds
Zero offset
User adjustable over the full display
range
User calibration
2-point gain & offset
Notes
(1) Calibration accuracy quoted over full ambient operating
range and for all input linearisation types.
(2) Contact SSI for details of availability of custom downloads for
alternative sensors.
Sample time:
9hz (110ms)
Isolation:
264Vac double isolation from the PSU
and communications
Excitation:
10Vdc +7%
Sensitivity:
1.4 to 4mV/V
Input span:
-27% to +127% of full scale (approx. –