9.3 Alarm Parameters
Four alarms are available. Parameters do not appear if the Alarm Type = None. The following table shows the
parameters to set up and configure alarms.
ALARM LIST
‘ALARM’
Name
Scrolling Display
Parameter Description
Value
Default
Access
Level
A1.TYP
ALARM 1 TYPE
Selects the type of alarm
none Alarm not configured As order
code
Conf
Hi
Full Scale High
Lo
Full Scale Low
r.roc Rising rate of
change
F.roc Falling rate of
change
A1.---
ALARM 1
SETPOINT
Alarm 1 threshold value.
The last three characters show the
type of alarm configured from the
above list
Instrument range
0
L3
A1.STS
ALARM 1
OUTPUT
Indicates the status of the alarm
OFF
Alarm off
Read
only
On
Alarm on
A1.HYS
ALARM 1
HYSTERESIS
See description at the beginning of
this section
0 to 9999
Conf
A1.LAT
ALARM 1
LATCHING TYPE
See description at the beginning of
this section
none Non-latching
As order
code
Conf
Auto Latching with
automatic resetting
Man
Latching with
manual resetting
Evt
Event (no alarm
flashing beacon but
messages can be
displayed)
A1.BLK
ALARM 1
BLOCKING
See description at the beginning of
this section
No
No blocking
No
Conf
yes
Blocking
A1.DLY
DELAY TIME
The alarm will not be indicated
until the set time has elapsed
0:00 to 99:59 mm:ss
0:59 = 59 seconds
99:59 = 99 minutes 59
seconds
0:00
A1.OFS
ALARM
SETPOINT
OFFSET
Applies a fixed offset to a full scale
high or full scale low alarm
setpoint. This may be useful when
used in conjunction with digital
communications, where a variable
value may be downloaded during
different parts of a process.
Instrument range
0
L3
The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4