11.2 Digital Communications Parameters
The following table shows the parameters available.
DIGITAL COMMUNICATIONS LIST ‘comms’
Name
Scrolling
Display
Parameter
Description
Value
Default
Access
Level
I D
MODULE
IDENTITY
Comms identity
none No module fitted
As order
code
Conf
L3 R/O
r232 EIA 232 Modbus interface
r485 EIA 485 Modbus interface
A D D R
ADDRESS
Communications
address of the
instrument
1 to 254
1
L3
B A U D
BAUD RATE
Communications
baud rate
1200 1200
9600
Conf
L3 R/O
2400 2400
4800 4800
9600 9600
19.20 19,200
P R T Y
PARITY
Communications
parity
none No parity
none
Conf
L3 R/O
Even Even parity
Odd
Odd parity
D E L A Y
RX/TX DELAY
TIME
To insert a delay
between Rx and Tx
to ensure that drivers
have sufficient time to
switch over.
Off
No delay
Conf
L3 R/O
On
Fixed delay applied
R E T R N
TRANSMITTED
PARAMETER
Master
communications
broadcast parameter.
See section 11.2.1.
none None
none
PV
Process Variable
R E G . A D
DESTINATION
ADDRESS
Parameter added in
the Slave address to
which the master
communications
value will be written
See section
11.5
.
0 to 9999
0