Super Systems 3L Series User Manual
Page 45
Series 3L Indicators
45
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
L.SENS
Configures the polarity of the logic
input channel A (0 = Normal, 1 =
Inverted)
12361
L.TYPE
(LB)
Logic Input B channel hardware
type
0 – None
1 – Logic Inputs
12362
L.D.IN
(LB)
Logic input B function)
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – Timer Reset
45 – Timer Run
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
12363
L.SENS
(LB)
Configures the polarity of the logic
input channel B (0 = Normal, 1 =
Inverted)
12377
ID
Comms Module Type
0 – None
1 – RS485
2 – RS232
12544
BAUD
Baud Rate
0 – 9600
1 – 19200
2 – 4800
3 – 2400
4 – 1200
12548
PRTY
Parity setting
0 – None
1 – Even
2 – Odd
12549
DELAY
RX/TX Delay – (0 = no delay, 1 =
delay) Select if a delay is required
between received and transmitted
comms messages. Sometimes
required when intelligent RS485
adaptors are used.
12550
RETRN
Comms Retransmission Variable
selection:
0 – Off
1 – Working Setpoint
2 – PV
3 – Output Power
4 – Error
12551
REG.AD
Modbus register address to
broadcast retransmission to. For
example if you wish to retransmit
the working setpoint from one
Series 3L to a group of slaves, and
receive the master working setpoint
into the slaves’ remote setpoint, set
this variable to 26 (the address of
the remote setpoint in the slave
units).
12552
Cal 3 offset
12558
Cal 4 offset
12559
1.ID
IO channel 1 hardware type
0 – None
1 – Relay
12672
1.FUNC
I/O Channel Function
0 – None (or Telemetry Output)
12674
1 – Digital Output
1.SRC.A
IO Channel 1 Source A
0 – None
1 – Alarm 1
2 – Alarm 2
3 – Alarm 3
4 – Alarm 4
5 – All Alarms (1-4)
6 – New Alarm
9 – Sensor Break Alarm
12677
1.SRC.B
IO Channel 1 Source B
As IO Channel 1 Source A (Modbus
address 12678)
12678
1.SRC.C
IO Channel 1 Source C
As IO Channel 1 Source A (Modbus
address 12678)
12679
1.SRC.D
IO Channel 1 Source D
As IO Channel 1 Source A (Modbus
address 12678)
12680
1.SENS
Configures the polarity of the input
or output channel (0 = Normal, 1 =
Inverted)
12681
IO1 high
12682
IO1 telemetry
12683
3.ID
Output 3 Type
0 – None
1 – Relay
12800
3.FUNC
Output 3 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
12803
3.SRC.A
Output 3 source A
As IO Channel 1 Source A (Modbus
address 12678)
12806
3.SRC.B
Output 3 source B
As IO Channel 1 Source A (Modbus
address 12678)
12807
3.SRC.C
Output 3 source C
As IO Channel 1 Source A (Modbus
address 12678)
12808
3.SRC.D
Output 3 source D
As IO Channel 1 Source A (Modbus
address 12678)
12809
3.SENS
Output 3 Polarity (0 = Normal, 1 =
Inverted)
12810
Output 3 telemetry
12812
4.TYPE
Output AA Type
0 – None
1 – Relay
13056
4.FUNC
Output 4 Channel function
0 – None (or Telemetry Output)
1 – Digital Output
13059
4.SRC.A
Output AA source A
As IO Channel 1 Source A (Modbus
address 12678)
13062
4.SRC.B
Output AA source B
As IO Channel 1 Source A (Modbus
address 12678)
13063
4.SRC.C
Output AA source C
As IO Channel 1 Source A (Modbus
address 12678)
13064
4.SRC.D
Output AA source D
As IO Channel 1 Source A (Modbus
address 12678)
13065
4.SENS
Output AA sense (0 = Normal, 1 =
Inverted)
13066