3 aa relay channel (aa) (output 4 fm relay), Aa relay channel (aa) (output 4 fm relay), Fm relay – Super Systems 3L Series User Manual
Page 30
Operations Manual
Series 3L
30
7.3 AA Relay Channel (AA) (Output 4 FM Relay)
This is a changeover relay. Connections are made to terminals AA, AB, and AC. OP4 beacon is operated from the AA
relay output channel. Output AA (4) has the same functionality as OP-1 and OP-3 – the parameters are repeated here
for clarity.
FM Relay
OUTPUT AA LIST ‘a a ’
Name
Scrolling
Display
Parameter
Description
Value
Defaul
t
Access
Level
4 . T Y P E
OUTPUT 4
TYPE
Displays the type of
output
reLy Relay output
reLy Read only
4.FUNC
OUTPUT 4
FUNCTION
The function may be
turned off, otherwise
set to
d.out
none
Disabled. If disabled no further
parameters are shown
Conf
d.out Digital output
4.SRC.A
OUTPUT 4
SOURCE A
Selects the source of
an event which will
operate the output
relay
The output status is
the result of an OR of
Src A, Src B, Src C,
and Src D
Up to four events can,
therefore, operate the
output
See section 7.1.2.
none No event connected to the
output
none Conf
4.SRC.B
OUTPUT 4
SOURCE B
1.--- Alarm 1
The --- indicates the
alarm type. If the
alarm is not
configured
AL.(Alarm no) is
shown
2.--- Alarm 2
4.SRC.C
OUTPUT 4
SOURCE C
3.--- Alarm 3
4.--- Alarm4
4.SRC.D
OUTPUT 4
SOURCE D
ALL.A All alarms
nw.AL Any new alarm
sbr
Sensor break alarm
Pwr.f Power fail
O.rng Output relay operates if the
indicator input is over range
4.SENS
OUTPUT 4
SENSE
To configure the
sense of the output
channel.
See also section 7.2.1
nor
Inv
Normal
Inverted
nor
Conf