8. Digital Inputs
The Series 3L comes with two digital inputs, LA and LB.
8.1 Digital Input Parameters
The input is typically from a voltage free contact, which can be configured to operate a number of functions as
determined by parameters in the LA and LB Lists:-
LOGIC INPUT LIST ‘LA’ / ‘LB’
Name
Scrolling
Display
Parameter Description
Value
Default
Access
Level
L.TYPE
LOGIC INPUT
TYPE
Input channel type
L.IP
Logic input
As order
code
Conf
Read only
L.D.I N
LOGIC INPUT
FUNCTION
To configure the function
of the digital input
none Input not used
Ac.AL
Conf
Ac.AL Alarm acknowledge
aL.in Alarm inhibit. See note 1
p.rst Peak value reset
free Freezes the current displayed
value
Loc.b Keylock
rec
Recipe select
UP
Remote key ‘Up’
dwn
Remote key ‘Down’
L.SENS
LOGIC INPUT
SENSE
To configure the polarity of
the input channel
nor
Normal
nor
Conf
Inv
Inverted
Note 1:
This input may be used, for example, in part of an automated process where it is required to prevent alarms from being
displayed during a particular part of the process. It should be used with care – blocking alarms or delayed alarms may
be an alternative.