5

SLOAN FLUSHOMETERS ARE ENGINEERED FOR QUIET

OPERATION. EXCESSIVE WATER FLOW CREATES NOISE,

WHILE TOO LITTLE WATER FLOW MAY NOT SATISFY THE

NEEDS OF THE FIXTURE. PROPER ADJUSTMENT IS MADE

WHEN THE PLUMBING FIXTURE IS CLEANSED AFTER

EACH FLUSH WITHOUT SPLASHING WATER OUT FROM

THE LIP AND A QUIET FLUSHING CYCLE IS ACHIEVED.

NEVER OPEN CONTROL STOP TO WHERE THE FLOW

FROM THE VALVE EXCEEDS THE FLOW CAPABILITY

OF THE FIXTURE. IN THE EVENT OF A VALVE FAILURE,

THE FIXTURE MUST BE ABLE TO ACCOMMODATE A

CONTINUOUS FLOW FROM THE VALVE.

!!! IMPORTANT !!!

Shut off Control Stop by turning handle

CLOCKWISE. Then remove

Flushometer Cover.

A

Lift out the inside Parts Assembly as

a complete unit. Reinstall Flushometer

Cover and tighten with wrench. Open

Control Stop. Turn on water supply to

flush line of any debris or sediment.

B

C

Shut off Control Stop and remove

Flushometer Cover. Reinstall Inside Parts

Assembly and Flushometer Cover. Tighten

Cover with wrench. Open Control Stop and

activate Flushometer Valve.

Adjust Control Stop to meet flow

rate required for proper cleansing

of fixture. Open Control Stop

COUNTERCLOCKWISE ONE

FULL turn from closed position. Activate

Flushometer. Adjust Control Stop after

each flush until the rate of flow delivered

properly cleanses the fixture.

D

5 - FLUSH OUT SUPPLY LINE AND ADJUST CONTROL STOP

1. Flushometer does not function (no flush).

A. Control Stop or Main Valve is Closed. Open Control Stop or Main Valve.

B. Handle or Push Button Assembly is worn. Install Sloan Handle Repair Kit

(C-70-A) or replace handle or push button.

C. Relief Valve is worn. Replace Royal Performance Kit (Royal) or Inside Parts Kit

(Regal).

2. Volume of water is not sufficient to siphon fixture.

A. Control Stop is not open wide enough. Adjust Control Stop for desired delivery of

water volume.

B. Urinal flushometer parts installed in a Closet flushometer. Replace inside Urinal

Flushometer parts with proper Closet Flushometer parts.

C. Incorrect Dual Filtered Diaphragm Assembly (Royal Flushometers) or Inside Parts

Kit (Regal Flushometers) is installed in flushometer; for instance, Urinal assembly

inside a Closet flushometer, or Low Consumption assembly inside a higher

consumption fixture. Determine the flush volume required by the fixture and

replace Royal Performance Kit or Inside Parts Kit. Use valve label and markings on

fixture for reference.

D. Water supply volume or pressure is inadequate. If no gauges are available to

properly measure supply pressure or volume of water at the Flushometer, then

remove the Relief Valve from the Dual Filtered Diaphragm Assembly (Royal) or

Inside Parts Kit (Regal), reassemble the flushometer and completely open the

Control Stop. If the fixture siphons, more water volume is required.

IMPORTANT — LAWS AND REGULATIONS PROHIBIT THE

USE OF HIGHER FLUSHING VOLUMES THAN LISTED ON

FIXTURE OR FLUSHOMETER.

If the fixture does not siphon or if a Low Consumption flush is required, steps must

be taken to increase the water supply pressure and/or volume. Contact the fixture

manufacturer for minimum water supply requirements of the fixture.

3. Flushometer closes off immediately.

A. Ruptured or damaged diaphragm. Replace Royal Performance Kit (Royal) or Inside

Parts Kit (Regal).

B.

For Regal Flushometers — An enlarged bypass orifice from corrosion or

damage. Replace Inside Parts Kit.

4. Length of flush is too short (Short Flush).

A.

For Regal Flushometers — The Diaphragm Assembly and Guide Assembly

are not hand tight. Screw the two assemblies hand tight.

B.

For Regal Flushometers — An enlarged bypass orifice from corrosion or

damage. Replace Inside Parts Kit.

C. Dual Filtered Diaphragm Assembly (Royal) or Inside Parts Kit (Regal) is damaged.

Replace Royal Performance Kit or Inside Parts Kit.

D. Incorrect Dual Filtered Diaphragm Assembly (Royal) or Inside Parts Kit (Regal) is

installed in Flushometer; for instance, Urinal assembly inside a Closet Flushometer,

or Low Consumption assembly inside a higher consumption fixture. Determine the

flush volume required by the fixture and replace Royal Performance Kit or Inside

Parts Kit. Use valve label and markings on fixture for reference.

E. Handle or Push Button Assembly is worn. Install Sloan Handle Repair Kit

(C-70-A) or replace handle or push button.

5. Length of flush is too long (Long Flush) or continuous.

A.

For Royal Flushometers — Metering bypass hole in Diaphragm is

clogged. Remove the Dual Filtered Diaphragm Assembly. Remove the Primary

and Secondary Filter Rings from the Diaphragm and wash under running water.

Replace Royal Performance Kit if cleaning does not correct the problem.

B.

For Regal Flushometers — Relief Valve (A-19-A) is not seating properly or

bypass orifice is clogged. Disassemble the working parts and wash thoroughly.

NOTE: SIZE OF THE ORIFICE IN THE BYPASS IS OF UTMOST

IMPORTANCE FOR THE PROPER METERING OF WATER

INTO THE UPPER CHAMBER OF THE FLUSHOMETER. DO

NOT ENLARGE OR DAMAGE THIS ORIFICE. REPLACE INSIDE

PARTS KIT IF CLEANING DOES NOT CORRECT PROBLEM.

C. Supply line water pressure has dropped and is not sufficient to close the valve.

Close Control Stop until pressure is restored.

D. Dual Filtered Diaphragm Assembly (Royal) or Inside Parts Kit (Regal) is damaged.

Replace Royal Performance Kit or Inside Parts Kit.

E. Incorrect Dual Filtered Diaphragm Assembly (Royal) or Inside Parts Kit (Regal) is

installed in Flushometer; for instance, Urinal assembly inside a Closet flushometer,

or Low Consumption assembly inside a higher consumption fixture. Determine the

flush volume required by the fixture and replace Royal Performance Kit or Inside

Parts Kit. Use valve label and markings on fixture for reference.

F. White Closet Relief Valve has been used in a Urinal flushometer. Replace Closet

Relief Valve (A-19-AC) with Black Urinal Relief Valve (A-19-AU).

G. Inside Cover is cracked or damaged. Replace the Inside Cover (A-71).

H. Conditions in the piping system may contribute to the noise. A degree of high

pressure in the piping may be relieved by adjustments to Control Stop. Other

noises created by loose pipes, lack of air chambers, inadequate pipe sizes, etc.,

are problems that must be discussed with the building engineer.

6. Chattering noise is heard during flush.

A. Inside Cover is damaged. Replace Inside Cover (A-71).

B.

For Regal Flushometers — A-156-A Segment Diaphragm has been

installed upside-down. Reposition the Segment Diaphragm properly (see markings

on the Diaphragm).

7. Leaking at Handle or Push Button Assembly.

A. The B-39 Seal is worn or deteriorated. Install new B-39 Seal.
NOTE: The B-39 Seal will easily slide onto the B-40 Bushing if

it is wet.

B. Handle gasket has been omitted. Install A-31 Handle Gasket or Sloan Handle

Repair Kit (C-70-A).

C. Valve Handle Bushing is worn. Install Sloan Handle Repair Kit (C-70-A).

When further assistance is required, please contact your

local Sloan Representative or Sloan Technical Support at:

1-888-SLOAN-14 (1-888-756-2614)

or visit us online at: www.sloanvalve.com

TROUBLESHOOTING GUIDE

NEVER OPEN THE CONTROL STOP TO

WHERE THE FLOW FROM THE VALVE EXCEEDS

THE FLOW CAPABILITY OF THE FIXTURE. IN THE

EVENT OF A VALVE FAILURE, THE FIXTURE MUST

BE ABLE TO ACCOMMODATE A CONTINUOUS

FLOW FROM THE VALVE.