beautypg.com

Pat 2000i – Seaward PAT2000i User Manual

Page 26

background image

MAINTENANCE

The PAT2000i is a rugged quality instrument, however care should be taken, failure to
do so will reduce the instruments life and hinder its reliability.

• Always check all test leads for signs of damage prior to use.
• Keep the instrument clean and dry.
• Avoid testing in conditions of high electrostatic or electromagnetic fields.
• Check memory for corruption prior to each period of operation. If in doubt clear

memory.

• No attempt should be made to gain access to the instrument while under test

conditions.

• Maintenance should only be performed by an authorised recognised member of

personnel.

The PAT2000i contains no user replaceable parts.

NOTE: Warranty excludes the internal rechargeable battery.

Should the PAT2000i require service, repair or calibration return the equipment to a
recognised dealer or to

Seaward Electronic Limited
Bracken Hill,
South West Industrial Estate,
Peterlee,
County Durham,
SR8 2JJ,
England.

The product should be returned post paid where, upon receipt, the owner will be
advised of any costs prior to work commencing.

SPECIFICATION

Safety Earth Test.

Measuring Range :

10m Ohms - 20.0 Ohms,1 milli-ohm resolution

Accuracy:

+10% +2 digits on 1Ohm range

Test Voltage:

6Vrms nominal open circuit

Output Current:

6.0,12.0 and 25A nominal into short circuit

Pass Range:

0.1, and 0.5 Ohms in manual and automatic modes

Earth Screen Test.

Measuring Range :

10m Ohms - 20.0 Ohms, 1 milli-ohm resolution

Accuracy:

+10% +2 digits on 1 ohm range

Test Voltage:

100mV rms nominal open circuit

Output Current:

100mA nominal into short circuit

Pass Range:

0.1, and 0.5 Ohms in manual and automatic modes

Insulation Test.

Measuring Range :

0.1 - 300 Mohms

Accuracy:

+8% +2 digits 0.1-50 Mohm

Test Voltage:

500Vdc nominal

Pass Range:

0.5 Mohms Class l,1.0 Mohms Class ll.

PAT 2000i

Portable Appliance Tester

23