Troubleshooting and customer service

13.1 Troubleshooting and customer service

The unit has been manufactured using state-of-the-art production methods and has been tested several

times to ensure that it works properly. However, in the event that malfunctions should occur, the unit should

be checked against the list below. Please inform your dealer if the unit is still not working correctly after all of

the functional checks have been performed.

Fault description

Cause

Remedy

System does not function

Power supply correct?

Switch electricity off/on and check

voltage

Cable connections correct?

Check connections and replace if nec-

essary

Fuse correct?

Check fuses and replace if necessary

High pressure fault

Excess refrigerant

Refill

Condenser too hot

Reduce temperature in the storage

tank

Low pressure alarm

Refrigerant level low

Check circuit for leaks

2. Refrigerant filter/capillary blocked Replace filter or capillary tube

Suction air temperature too cold/not

present

Check air supply/temperature

No hot water being supplied Shut-off cocks for water supply

closed

Open shut-off cocks

Water pressure too low

Increase water pressure

Display remains dark

Safety temperature limiter has trig-

gered

Reduce the temperature in the storage

tank