The hot water heat pump is fitted with a 1.3 m

2

heating battery as standard. This enables connec-

tion with an existing heating system. The option

therefore exists of also heating the hot water with

the existing boiler. For this purpose, the heating

battery supply and return flow are connected with

the heating system.

NOTICE!

In order to prevent heat losses in the hot water

heat pump, the heating connection and the hot

water connection are to be professionally con-

nected with syphoning (min. 200 mm), in order

to prevent single tube gravity circulation!

NOTICE!

When connecting the hot water heat pump

with a boiler:
When operating the circulation pump, the pow-

erful boiler circulation can result in the trans-

port of heat from the hot water heat pump into

the boiler. In order to prevent this, fit a check

valve after the circulation pump of the heat

generator!

Condensate water drain

The cooling of the air in the evaporator results in

condensate water forming. The condensate drain

on the hot water heat pump must be transported

away from the heat pump with plastic pipes and an

uninterrupted flow of the condensate must be guar-

anteed. Depending on the humidity, up to approx.

0.25 l/h of condensate may arise. The condensate

drain must not be permanently connected with a

duct connection because the heat exchanger fins

and parts of the hot water heat pump may be

attacked by the ammonia vapours rising from the

duct.