4.3 Set-up
WARNING!
The set-up of the heat pump may only be car-
ried out by trained specialists.
n
The heat pump must be set up indoors.
n
A condensate drain must be available.
n
The heat pump must be set up horizontally.
n
Suitable installation sites are dry, clean, frost-
free rooms with a level floor, which exhibit a
height of no less than 2.15 m.
n
The heat pump must be installed on a firm,
level surface.
n
The surface must possess sufficient load-
bearing capacity for the weight of the heat
pump.
n
The height-adjustable feet can be used to level
the heat pump precisely .
n
The heat pump is to be mounted in such a way
that sufficient space is available on all sides for
purposes of installation and maintenance.
n
In order to keep output losses to a minimum,
the heat pump should be set up as close as
possible to the hot water consumer.
n
If the supply and exhaust air from neighbouring
rooms is to be used, ensure that no positive or
negative pressure can build up in the rooms.
Use of a circulation system
It is not advisable to use a circulation system
because the loss per running metre of piping can
be approx. 25- 30 Watts. However, if such a
system is installed then a timer and a thermostat
should be installed with it.
NOTICE!
To avoid damage to the system, the installation
location must be dry, capable of carrying the
load and frost-free.
NOTICE!
Keep the hot water heat pump and lines free of
frost
Fig. 4: Floor mounting
Minimum distances
350
200
200
2250
Fig. 5: Minimum distances in mm
Suction air
The suction air must not be loaded with aggressive
substances (ammonia, sulphur, halogen, chlorine,
etc.)! This can cause the destr. of machine parts!
Air connection
The air take-off point should be selected with con-
sideration to a high average air temperature and
the requisite air volume of 350 m
3
/h. Air inlets and
outlets are at the top. In order to keep the air
resistance to a minimum, the air intake and
exhaust duct should be configured as straight as
possible, with a minimum smooth tube cross-sec-
tion of Ø 150 mm. The entire tube length for the
REMKO RBW