Remko rbw – REMKO RBW 300 PV User Manual
Page 32

Parameter
Parameter list (expert level)
No.
Description
Code Para-
meter Value
Range
1
Factory setting
/
/01
2
Factory setting
/02
3
Factory setting
C
C01
0
4
Factory setting
C02
5
5
Factory setting
C03
-1
6
Factory setting
C04
5
7
Start defrost temperature (evaporator)
d
d01
-3°C
-30~0°C
8
End defrost temperature (evaporator)
d02
13°C
2~30°C
9
Time between defrosts
d03
45 min
30~90 min
10
Max. defrosting period
d04
8 min
1~12 min
11
Min. defrosting period Eco defrosting (recirculation
defrosting)
d05
3 min
1~10 min
12
Defrosting mode 1 = recirculation, 2 = heat gas
d06
0
0~2
13
Ambient temp. at start of heat gas defrosting
d07
4°C
-10~20°C
14
Setpoint for legionella function
g
g01
60°C
30~70°C
15
Duration of legionella function
g02
0 min
0~90 min
16
Time start of legionella function
g03
0 h
0~23 h
17
Time interval (day) of legionella function
g04
7
7~99 days
18
Factory setting
E
E01
1
19
Factory setting
E02
20
Factory setting
E03
21
Factory setting
E04
100
22
Factory setting
E05
23
Automatic restart after power failure
H
H01
1
0-no/1-yes
24
Factory setting
H02
25
Factory setting
H03
26
Factory setting
H04
27
Factory setting
H05
28
Factory setting
H06
1 h
29
Temperature unit
H07
0
0-°C/1-F
REMKO RBW
32