REMKO RBW 300 PV User Manual

Page 33

background image

Parameter list (expert level) - continued

No.

Description

Code Para-

meter Value

Range

30

Used storage tank probe solar

n

n01

0

0-bottom/1-top

31

Min. run-time solar pump

n02

15 min

1-30 min

32

Start temperature difference solar

n03

5 K

0~20 K

33

Night reduction

n04

0

0-no/1-yes

34

Start time night reduction

n05

00 h

00~23 h

35

End time night reduction

n06

06 h

00~23 h

36

Start temperature night reduction

n07

70°C

40~90°C

37

End temperature night reduction

n08

10°C

1~40°C

38

Max. storage tank temperature for the solar

drainage valve

n09

80°C

50~90°C

39

Max. storage tank temperature solar pump stop

n10

84°C

50~90°C

40

Solar pump operation storage tank temperature-

independent

n11

0

0-no/1-yes

41

Start collector temperature solar pump

r

r01

55°C

10~60°C

42

Setpoint kitchen mode

r02

45°C

40~48°C

43

Hysteresis setpoint HW water

r03

5 K

1~20 K

44

Parallel operation heat pump/heating coil

r04

0

0-no/1-yes

45

Switch-on temperature elec. Heating coil

r05

55°C

30~90°C

46

Switch-on delay elec. Heating coil

r06

200 min

0~450 min

47

Elec. heating coil replaces compressor

r07

0

0-no/1-yes

48

Lower heat pump usable limit

r08

-5°C

-20~10°C

49

Bivalence point elec. heating coil without delay

r09

10°C

0~30°C

50

Bivalence point elec. heating coil with time delay r06

r10

25°C

10~40°C

51

Run-time circulation pump

r11

60 s

0~255 s

52

Lower heat pump emergency stop usable limit

r12

-15°C

-5~-30°C

53

Heat limit kitchen mode

r13

56°C

50~56°C

54

Setpoint with PV yield

r14

45°C

10-60°C

55

Removes on/off switch status

S

S01

Status

CL/OP

56

OHP switch (over heat protection) condenser

S02

Status

CL/OP

57

Not assigned

58

Error output high pressure alarm switch status

S04

Status

CL/OP

59

Switch status elec. Heating coil

S05

Status

CL/OP

60

Not assigned

33