intake and exhaust air should not be more than 12

m, whereby the installation of no more than 3 right-

angled elbows is permitted. The entire tube length

must be reduced by 1 m with every additional

elbow. In order to prevent the discharge of conden-

sate water, the air lines must be laid horizontally or

with a slight downward gradient towards the suc-

tion/blow-out openings, or the installation of an

evaporation pouch is required.

Air duct lines

n

Suction and blow-out lines from smooth tube,

Ø 150 mm.

n

The max. overall length of the pipe

(suction and exhaust air) is 12 m with a

max. 3 x 90° elbows

n

The entire tube length must be reduced by 1 m

for every additional elbow!

n

The pipes incl. accessories must be provided

by the customer (ventilation pipe produced

from plastic, aluminium or galvanised sheet

steel, etc.).

n

The pressure loss must not exceed

a max. 50 kPa.

NOTICE!

During operation of the domestic hot water heat pump in the recirculation mode, the volume must be at
least 30 m

3

. (See Fig. 6 pictures A-C)