Appendix f - vcm-x bacnet parameters, Pt-link ii bacnet, Technical guide pt-link ii interface 46 – Orion System PT-Link II BACnet2 User Manual
Page 46
PT-Link II BACnet
®
Technical Guide
PT-Link II Interface
46
Appendix F - VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
Parameter
Name
Object
Description
Limits
On Board
Relay 1
OnRly1
BI: 127
Current status of
relay 1.
On Board
Relay 2
OnRly2
BI: 128
Current status of
relay 2.
On Board
Relay 3
OnRly3
BI: 129
Current status of
relay 3.
On Board
Relay 4
OnRly4
BI: 130
Current status of
relay 4.
On Board
Relay 5
OnRly5
BI: 131
Current status of
relay 5.
Expansion
Relay 1
ExRly1
BI: 133
Current status of
relay 6.
Expansion
Relay 2
ExRly2
BI: 134
Current status of
relay 7.
Expansion
Relay 3
ExRly3
BI: 135
Current status of
relay 8.
Expansion
Relay 4
ExRly4
BI: 136
Current status of
relay 9.
Expansion
Relay 5
ExRly5
BI: 137
Current status of
relay 10.
Expansion
Relay 6
ExRly6
BI: 138
Current status of
relay 11.
Expansion
Relay 7
ExRly7
BI: 139
Current status of
relay 12.
Expansion
Relay 8
ExRly8
BI: 140
Current status of
relay 13.
Expansion
Relay 9
ExRly9
BI: 141
Current status of
relay 14.
Expansion
Relay 10
ExRly10
BI: 142
Current status of
relay 15.
Expansion
Relay 11
ExRly11
BI: 143
Current status of
relay 16.
Expansion
Relay 12
ExRly12
BI: 144
Current status of
relay 17.
Expansion
Relay 13
ExRly13
BI: 145
Current status of
relay 18.
Expansion
Relay 14
ExRly14
BI: 146
Current status of
relay 19.
Expansion
Relay 15
ExRly15
BI: 147
Current status of
relay 20.
Expansion
Relay 16
ExRly16
BI: 148
Current status of
relay 21.