Appendix f - vcm-x bacnet parameters, Pt-link ii bacnet, Technical guide pt-link ii interface 42 – Orion System PT-Link II BACnet2 User Manual
Page 42
PT-Link II BACnet
®
Technical Guide
PT-Link II Interface
42
Appendix F - VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
Parameter
Name
Object
Description
Limits
Alarm
Status
AlmSts
AI: 1
See Alarm
Group Bits on
page 47.
Control
Status
CtrlSts
AI: 4
Current operational
status.
Occupied/
Mode
Enable
Cooling
Setpoint
Mirror
ClSt
AI: 7
Occupied/ Mode
Enable Cooling
Setpoint Mirror.
Control
Temperature
CtrlTp
AI: 9
Current value of the
control temperature
sensor.
Duct Static
Pressure
DuctPr
AI: 14
Current value of the
duct static pressure
sensor.
Economizer
Position
EcoPos
AI: 16
Current position
of the economizer
damper.
Occupied/
Mode
Enable
Heating
Setpoint
Mirror
HtSt
AI: 31
Occupied/ Mode
Enable Heating
Setpoint
Mirror.
Modulating
Gas Valve
Position
MdHt-
2Pos
AI: 38
Current position
of MODGAS II
modulating gas
valve control.
On Board
Relays
OnRlys
AI: 44
See page 47.
Outdoor Air
Dewpoint
OaDwpt
AI: 47
Current calculated
outdoor air
dewpoint added on
version 1.09.
Outdoor Air
Humidity
OaRh
AI: 52
Current value of the
outdoor humidity
sensor.
Outdoor Air
Temperature
OaTp
AI: 54
Current value of the
outdoor tempera-
ture sensor.
Outdoor Air
Wetbulb
OaWtbl
AI: 55
Current calculated
value of the outdoor
wetbulb
temperature.
Reheat
Value
Position
Rt2Pos
AI: 60
Current position of
MHGRV modulat-
ing hot gas reheat
valve control.
Relief
Pressure
RfPr
AI: 62
Current value of the
building pressure
sensor.
Return Air
Temperature
RaTp
AI: 64
Current value of the
return temperature
sensor.
BACnet Properties for the VCM-X Controller
Parameter
Name
Object
Description
Limits
Indoor
Humidity
InRh
AI: 67
Current value of
the indoor humidity
sensor.
Space
Temperature
SpcTp
AI: 72
Current value of the
space temperature
sensor.
Current
Supply Air
Setpoint
SaTpStM
AI: 82
Current SAT
Cooling or Heating
setpoint if there
is no reset source;
Current calculated
SAT setpoint with
Reset Source.
Supply Air
Temperature
SaTp
AI: 83
Current value of the
supply air
temperature sensor.
Temperature
Demand
TpDmnd
AI: 84
Based on the
comparison
between the
current Control
Temperature and
the Heating or
Cooling Setpoint
Temperatures. Does
not work for supply
air control
VFD
Blower Fan
VfdBw-
Pos
AI: 88
Current position of
the VFD blower fan
signal.
VFD
Relief Fan
VfdExPos
AI: 89
Current position of
the VFD relief
fan signal.
Application
Software
Version
AppVer
AI: 99
Current version of
the software in the
unit.
Alarm
Group 1
AlrmGrp1
AI: 104
See Alarm
Group Bits on
page 47.
Alarm
Group 2
AlrmGrp2
AI: 105
See Alarm
Group Bits on
page 47.
Alarm
Group 3
AlrmGrp3
AI: 106
See Alarm
Group Bits on
page 47.
Dewpoint
Setpoint
Mirror
DptStM
AI: 110
Mirror of the DPtSt
“read only.”
External
Relays 1-2
ExRlys12
AI: 111
See page 47.
External
Relays 3-4
ExRlys34
AI: 112
See page 47.
Indoor Rh
Setpoint
Mirror
InRhStM
AI: 114
Mirror of the
InRhSt “read only.”