Appendix d - vcb-x bacnet parameters, Pt-link ii interface pt-link ii bacnet, Technical guide 33 – Orion System PT-Link II BACnet2 User Manual
Page 33

PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
33
Appendix D - VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
Alarm
Group 1
AlmGrp1
AI: 104
See Alarm
Group Bits on
page 39.
Alarm
Group 2
AlmGrp2
AI: 105
See Alarm
Group Bits on
page 39.
Alarm
Group 3
AlmGrp3
AI: 106
See Alarm
Group Bits on
page 39.
Alarm Status
AlmSts
AI: 1
Indicates that
there is an
alarm.
0 = Off
1 = On
See Alarm
Group Bits on
page 39.
Application
Software
Version
AppVer
AI: 99
Current version
of the software
in the unit.
Unit Mode
UnitMode
AI:123
See Unit Mode
Bits on page
39.
Building
Pressure
BuildPr
AI:272
Current value
of the building
pressure sensor.
Building
Pressure
Setpoint
RfPrSt
AV:118
Current
Building
Pressure
Setpoint.
-.20
.20
CO
2
CO2
AI:271
Current CO
2
Level.
CO
2
Minimum
Setpoint
CO2MinLv
AV:287
This is the
threshold CO
2
level at which
the Economizer
Min Damper
Position
Setpoint will
begin to be
reset higher.
0
2000
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
CO
2
Maximum
Setpoint
CO2
MaxLv
AV:288
This is the CO
2
level at which
the Economizer
Min Damper
Position will
be reset to the
Economizer
Max Position
in High CO
2
.
In between the
Min and Max
CO
2
levels the
Economizer
Min Damper
Position will be
proportionally
reset between
the confi gured
Min Damper
Position and the
Max Position in
High CO
2
.
0
2000
Coil
Temperature
CoilTp
AI: 181
Current coil
temperature
reading.
Coil
Temperature
Offset
ColTpOft
AV:284
If the
Coil
Temperature
Sensor is
reading
incorrectly, you
can use this
option to
enter an offset
temperature to
adjust the
Sensor’s
Temperature.
-100
100
High Coil
Temperature
Setpoint
HiClTpSt
AV:296
This is the
highest that the
Coil
Temperature
will be reset to
during Space
Humidity Reset
of the Coil
Suction
Temperature
Setpoint.
Produces a
dew point in
the supply air
approximately
10˚F above this
setpoint.
35
70
Cooling Low
Reset Source
ClLoRt
AV: 326
Low Cool
Reset Source
Setpoint
1
150
Cooling High
Reset Source
ClHiRt
AV: 327
High Cool
Reset Source
Setpoint
1
150
Revised 4/3/13