Pt-link ii bacnet, Technical guide pt-link ii interface 40 – Orion System PT-Link II BACnet2 User Manual
Page 40

PT-Link II BACnet
®
Technical Guide
PT-Link II Interface
40
Appendix E - VCM-X Modular & WSHP & RNE BACnet Parameters
BACnet Properties for VCM-X Modular
Parameter
Name
Object
Description
Limits
Modulating
Compressor 2
MdCmp2
AI: 206
Current position
of the 2nd Stage
of Compressor
Modulation.
Head
Pressure 1
HdPr1
AI: 207
Head Pressure for
1st Compressor
Head
Pressure 2
HdPr2
AI: 208
Head Pressure for
2nd Compressor
Condenser
Fan 1
CdFan1
AI: 209
Condenser Fan 1
Signal Status
Condenser
Fan 2
CdFan2
AI: 210
Condenser Fan 2
Signal Status
Remote VFD
Reset
RmVFDPos
AV: 258
Remote VFD
Position Reset
-1
100
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Modulating
Compressor 2
MdCmp2
AI: 206
Current position
of the
2nd Stage of
Compressor
Modulation.
Head Pressure 1
HdPr1
AI: 207
Head Pressure
for
1st Compressor
Head Pressure 2
HdPr2
AI: 208
Head Pressure
for
2nd Compressor
Condenser
Fan 1
CdFan1
AI: 209
Condenser Fan 1
Signal Status
Condenser
Fan 2
CdFan2
AI: 210
Condenser Fan 2
Signal Status
Water Temp. A
WaterTpA
AI: 220
Current water
temperature of
refrigerant for
System A.
Water Temp. B
WaterTpB
AI: 221
Current water
temperature of
refrigerant for
System B.
Remote VFD
Reset
RmVFDPos
AV:
258
Remote VFD
Position Reset
-1
100
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Compressor A1
Low Suction
Pressure Alarm
A1LSPAlm
BI: 222
Alarm that
indicates
Suction Pressure
for
Compressor A1
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Compressor A1
Lockout Alarm
A1LktAlm
BI: 223
Alarm that
indicates
Compressor A1
is locked out.
Compressor A2
Low Suction
Pressure Alarm
A2LSPAlm
BI: 224
Alarm that
indicates
Suction Pressure
for
Compressor A2
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Compressor A2
Lockout Alarm
A2LktAlm
BI: 225
Alarm that
indicates
Compressor A2
is locked out.
Compressor B1
Low Suction
Pressure Alarm
B1LSPAlm
BI: 226
Alarm that
indicates
Suction Pressure
for
Compressor B1
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Compressor B1
Lockout Alarm
B1LktAlm
BI: 227
Alarm that
indicates
Compressor B1
is locked out.
Compressor B2
Low Suction
Pressure Alarm
B2LSPAlm
BI: 228
Alarm that
indicates
Suction Pressure
for
Compressor B2
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Compressor 4
Lockout Alarm
B2LktAlm
BI: 229
Alarm that
indicates
Compressor B2
is locked out.
NOTE:
The following points for the VCM-X Modular, VCM-X
WSHP & RNE Controllers are additional points. All
points and property identifi ers in the VCM-X Con-
troller table (pages 42-47) also apply to the VCM-X
Modular, VCM-X WSHP, and RNE Controllers.
Revised 10/11/12