Appendix d - vcb-x bacnet parameters, Pt-link ii interface pt-link ii bacnet, Technical guide 35 – Orion System PT-Link II BACnet2 User Manual
Page 35
PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
35
Appendix D - VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
Head
Pressure
Setpoint in
Cooling Mode
ClHdPrSt
AV:293
This is the
Head Pressure
Setpoint the
unit will control
to in the
Cooling Mode.
240
PSI
420
PSI
Head
Pressure
Setpoint
in Reheat
Mode
HtHdPrSt
AV:294
This is the
Head Pressure
Setpoint the
unit will control
to in the De-
humidifi cation
Reheat Mode.
240
PSI
420
PSI
Heating Low
Reset Source
HtLoRt
AV: 328
Low Heat Reset
Source Setpoint
1
150
Heating High
Reset Source
HtHiRt
AV: 329
High Heat
Reset Source
Setpoint
1
150
Heating
Enabled
HtEnbl
AI: 30
Status that
indicates that
mechanical
heating is
enabled.
Heating
Setpoint
Mirror
HtSt
AI: 31
Occupied
Heating Mode
Enable Setpoint
Mirror.
Indoor
Humidity
InRh
AI: 67
Current value
of the indoor
humidity
sensor.
Indoor
Humidity
Setpoint
InRhSt
AV:289
If Coil Temp
Reset is being
used this is
also the lowest
Space RH value
that
corresponds
to the Hi Coil
Temp Setpoint.
0
100
High Indoor
Humidity
Reset Limit
HiInRh
AV:292
During Coil
Temp Reset,
this is the
highest Space
RH value that
corresponds to
the Low Coil
Temp Setpoint.
0
100
Indoor
Humidity
Setpoint
Mirror
InRhStM
AI: 114
Mirror of the
InRhSt “read
only.”
Leaving Water
Temperature
LvWtrTp
AI:278
Leaving Water
Temperature
Value
BACnet Properties for the VCB-X Controller
Parameter
Name
Object
Description
Limits
Low
Ambient
Relay
Setpoint
LWAmbnt
AV:285
Temperature at
which the Low
Ambient Relay
will activate in
the Occupied
or Unoccupied
Mode.
-30
70
Modulating
Cooling
Position
MdClPos
AI: 115
Current
position of the
modulating
cooling signal
(Chilled water
or digital
compressor).
Modulating
Gas Valve
Position
MdGs
VPos
AI:274
Current
position of
MODGAS
modulating gas
valve control.
Modulating
Heating
Position
MdHtPos
AI: 116
Current
position of the
modulating
heating signal
(hot water or
SCR heat).
Morning
Warm-Up
Setpoint
WmupTg
AV:281
In a VAV
application,
upon entering
the
occupied mode,
the Warm-up
Demand will
be activated if
the return air
temperature
falls one degree
below this
setpoint.
50
90
Occupied
Cooling
Setpoint
OcpClSt
AV: 42
If the control
temperature
rises one degree
above this
setpoint, the
control will ac-
tivate the cool-
ing demand. If
the control
temperature is
the Supply Air
Sensor, then the
cooling demand
is always
active.
1
110