RNE Modular Controller Field Technical Guide

RNE CONTROLLER TROUBLESHOOTING

75

OE275-01 Suction Pressure Transducer Testing

OE275- 01 Suction Pressure

Transducer Testing for R22 and R410A

Refrigerant

The Evaporator Coil Temperature is calculated by converting the Suc-
tion Pressure to Temperature. The Suction Pressure is obtained by using
the OE275-01 Suction Pressure Transducer, which is connected into the
Suction Line of the Compressor.

Use the voltage column to check the Suction Pressure Transducer
while connected to the VCM-X Expansion Module. The RNE and the
VCM-X Expansion Module must be powered for this test. Read voltage
with a meter set on DC volts. Place the positive lead from the meter
on the PR OUT terminal located on the VCM-X Expansion Module
terminal block. Place the negative lead from the meter on the ground
(GND) terminal located adjacent to the PR OUT terminal on the VCM-X
Expansion Module terminal block. Use a refrigerant gauge set and/or an
accurate electronic thermometer to measure the temperature or suction
line pressure near where the Suction Pressure Transducer is connected
to the suction line. Measure the Voltage at the terminals PR OUT and
GND terminals and compare it to the appropriate chart depending on
the refrigerant you are using. If the temperature/voltage or pressure/volt-
age readings do not align closely with the chart, your Suction Pressure
Transducer is probably defective and will need to be replaced.

See the OE275-01 Suction Pressure Transducer, Pressure, Temperature,
and Voltage Chart for R22 and R410A Refrigerant testing (Tables 8
and 9). The charts show a temperature range from 20°F to 80°F. For
troubleshooting purposes, the DC Voltage readings are also listed with
their corresponding temperatures and pressures.

OE275-01 Suction Pressure Transducer

Coil Pressure

– Temperature – Voltage Chart for R22 Refrigerant

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

20.00

31.13

1.0

55.32

93.39

2.0

20.00

37.36

1.1

58.86

99.62

2.1

20.46

43.58

1.2

62.13

105.84

2.2

25.71

49.80

1.3

65.27

112.07

2.3

30.84

56.03

1.4

68.42

118.29

2.4

35.41

62.26

1.5

71.39

124.52

2.5

39.98

68.49

1.6

75.20

130.75

2.6

44.00

74.71

1.7

77.00

136.97

2.7

48.00

80.94

1.8

79.80

143.20

2.8

51.78

87.16

1.9

80.00

149.42

2.9

Table 9: Coil Pressure/Voltage/Temp for OE275-01
Suction Pressure Transducers - R410A Refrigerant

Table 8: Coil Pressure/Voltage/Temp for OE275-01
Suction Pressure Transducers - R22 Refrigerant

OE275-01 Suction Pressure Transducer

Coil Pressure

– Temperature – Voltage Chart for R410A Refriger-

ant

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

Temper

atur

e

°F

Pr

essur

e

PSI

Signal DC V

olts

21.19

80.94

1.8

59.03

168.10

3.2

24.49

87.16

1.9

61.17

174.32

3.3

27.80

93.39

2.0

63.19

180.55

3.4

30.99

99.62

2.1

65.21

186.78

3.5

33.89

105.84

2.2

67.23

193.00

3.6

36.80

112.07

2.3

69.24

199.23

3.7

39.71

118.29

2.4

71.15

205.46

3.8

42.30

124.52

2.5

72.95

211.68

3.9

44.85

130.75

2.6

74.76

217.91

4.0

47.39

136.97

2.7

76.57

224.14

4.1

49.94

143.2

2.8

78.37

230.36

4.2

52.23

149.42

2.9

80.18

236.59

4.3

54.50

155.65

3.0

56.76

161.88

3.1