Installation and wiring, Rne modular controller field technical guide, Or greentrol – Orion System RNE Modular Controller User Manual
Page 39
RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
39
Air Flow Monitoring Station Installation and Wiring
Figure 31: OE365-15-EBA - Airfl ow Monitoring Station To E-BUS Wiring
COMM
COMM
NET-
NET-
NET+
NET+
Airflow Measurement
Digital Transmitter Terminals
For Outdoor Air CFM
(Set Address Switch To 9)
Airflow Measurement
Digital Transmitter Terminals
For Return Air CFM
(Set Address Switch To 10)
Airflow Measurement
Digital Transmitter Terminals
For Supply Air CFM
(Set Address Switch To 11)
COMM
NET-
NET+
RNE Controller
OE365-15-EBA
E-BUS Adapter Board
HSSC Cable Connect To
RNE E-BUS Port
I2C DIGITAL
SENSOR
I2C
EXPANSION
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
WattMaster Label
#LB102033-01
AI1 AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
EMERGENCY SHUTDOWN
AI1 SET
AI1
THERM
THERM
4-20mA
0-10V
0-5V
ANALOG INPU
JUMPER
SETTINGS
Connect To
RNE E-BUS Port
Air Flow Monitoring Station
Installation and Wiring
The OE365-15-EBA E-BUS Adapter Board is used to connect selected
Air Flow Monitoring Stations to the RNE Controller. Currently, there
are two Air Flow Monitoring Station options that are supported in our
standard software.
• EBTRON
®
- GTC-116 Series Air Flow Monitoring Station*
•
GreenTrol™ Automation – GA-200-N Module used with
any GF Series Air Flow Monitoring Station
The wiring for the two Air Flow Monitoring Stations are the same and
are shown in Figure 31.
*NOTE: When confi guring the GTC-116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”
NOTE: Up to 3 EBTRON
®
or GreenTrol
TM
Airfl ow Measure-
ment Digital Transmitters can be attached to each
Adapter Board.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) may be
required.