RNE Modular Controller Field Technical Guide
OVERVIEW
7
Parts and Descriptions
PART NO.
PART DESCRIPTION
ILLUSTRATION
PAGE
NO.
OE332-23E-RNE-A
RNE Controller
The RNE Controller provides 7 analog inputs, 2 analog outputs, and 5
relays. It presently allows for the addition of the VCM-X Expansion Mod-
ule, the 12 Relay Expansion Module, and hte 4 Binary Input Expansion
Module described below.
NOTE:
Set-up, programming, and monitoring of the RNE Controller
requires one of the following communication interfaces—Prism 2 Front-
End Software used with a personal computer, System Manager Touch
Screen II, or Modular Service Tool.
Page
18
OE333-23-EM
VCM-X Expansion Module
Includes: VCM-X Expansion Module mounted in plastic enclosure and
10 ft. I
2
C cable. The VCM-X Expansion Module adds VAV applications,
building pressure control, head pressure control, water source heat
pump monitoring, and other functions. It provides 4 additional analog
inputs, 2 binary inputs, 5 additional relays, and 3 analog outputs. It
connects with a modular cable to the RNE Controller.
Pages
26-28
OE358-23-12R
VCM-X 12 Relay Expansion Module
Includes: 12 Relay Expansion Module mounted in plastic enclosure
and 10 ft. I
2
C cable. The VCM-X 12 Relay Expansion Module adds 12
confi gurable relays to the RNE Control System. It connects to the RNE
Controller using the included I
2
C cable.
Page
38
OE356-01-BI
VCM-X 4 Binary Input Expansion Module
Includes: 4 Binary Input Expansion Module mounted in Snap Track and
10 ft. I
2
C cable. Use the 4 Binary Input Expansion Module if your HVAC
unit only requires a Smoke Detector/Firestat, Dirty Filter, Proof of Flow,
or Remote Forced Occupied Inputs or all of these 4 inputs and you don’t
need any of the other inputs or outputs provided by the OE333-23-EM
VCM-X Expansion Module. The module connects to the RNE Controller
using the included I
2
C cable.
Page
29
OE334-23-WSHP-X2
Water Source Heat Pump X2 Module
Includes: Water Source Heat Pump X2 Module in a plastic enclosure
with LCD display and E-BUS Modular cable. Provides monitoring and
compressor control for AAON Tulsa Water Source Heat Pump Units.
Used with the RNE Controller.
WATTMASTER CONTROLS
Y 102374 REV 0
S
MADE IN USA
Pages
41,44
OE370-23-FD-A
Full Digital Module
Includes: Full Digital Module in a plastic enclosure and E-BUS Modular
cable.Used with the RNE Controller. For AAON Tulsa units with multiple
Digital Scroll Compressors and that are not Water Source Heat Pump
Units.
www.orioncontrols.com
1003
1002
10uF
300
1
2
4
8
SERIA
L
#
C2
D3
D4
R7
R9
R11
R12
R13
R14
R23
R24
R25
R26
R28
R29
R30
SW1
D12
D13
R53
R54
TB3
C20
R34
R
50
SW2
+5V
SIG 2
GND
1003
1002
10uF
1003
1002
10uF
1003
1002
10uF
475
1
475
1
475
1
475
1
OF
F
OF
F
OP
T
ION
S
ALARM
ANALOG
STAT
+5V
COMM
GND
SIG 4
300
GND
BIN 2
R1
4
R2
4
GND
1002
1002
1002
1002
1002
1002
1002
1002
RELAYS
ADDRESS
SIG 3
+5V
GND
BIN 1
COM
+5V
SIG 1
R3
R4
Rc
AO1
AO2
PWM1-
PWM1+
PWM2-
PWM2+
.01uF
PWR
Pages
40,43
WA
RN
IN
G
OB
SE
RV
E
PO
LA
RI
TY
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
VCM
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01-A
Rev.: 1K
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
BI1 = EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
www.aaon.com
www.orioncontrols.com
VCM-X Expansion Module
Orion No.:OE333-23-EM
AAON No.:
R69190
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
A3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
I
POWER
RLY1
RLY2
RLY3
RLY4
RLY COM
EXP1
EXP2
24VAC
GND
EXPANSION BOARD
YS102228 REV 1
RELAY
RLY5
RLY6
RLY7
RLY8
RLY COM
RLY9
RLY10
RLY11
RLY12
RLY COM
MADE IN USA
SET JUMPER AS
SHOWN WHEN
THE 12 RELAY
EXPANSION MODULE
IS USED
ONLY
SET JUMPER AS
SHOWN WHEN BOTH
THE VCM EXPANSION
MODULE AND THE
RELAY EXPANSION
MODULE ARE USED
J1
J1
EXP1
EXP1
EXP2
EXP2
NOTE:
IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE RELAY OUTPUTS YOU
ARE CONNECTING TO THE RELAY EXPANSION
MODULE IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE)
FOR FUTURE REFERENCE.
®
WattMaster Label
#LB102043
I2C
EXPANSION
I2C
EXPANSION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
RLY 1 =
RLY 7 =
RLY 2 =
RLY 8 =
RLY 3 =
RLY 9 =
RLY 4 =
RLY 10 =
RLY 5 =
RLY 11 =
RLY 6 =
RLY 12 =
OE358-23-12R 12 RELAY EXPANSION MODULE
BI1
BI2
BI3
BI4
COM
VCM BIN EXP
BOARD
YS102364 REV1
24V
A
C
GND
PWR