Installation and wiring, Rne modular controller field technical guide 44, Water source heat pump module – Orion System RNE Modular Controller User Manual

Page 44: Zone

background image

Zone

Zone

INSTALLATION AND WIRING

RNE Modular Controller Field Technical Guide

44

Figure 36: RNE 120 - 140 Ton Unit Four Compressor WSHP Module Wiring

Water Source Heat Pump Module

RNE Units with DX Cooling will have either a Half VFD/Half Fixed
compressor confi guration or a Full VFD compressor confi guration. The
RNE 120 - 140 Ton units have four compressors and will have either
two VFD and two Fixed Compressors or will have four VFD Compres-
sors. The operation of these compressors is described in the Sequence
of Operation section of this manual.

For Water Source Heat Pump (WSHP) units, the outputs to the compres-
sors will always be wired from the Water Source Heat Pump Modules.
For RNE 120 - 140 Ton units, two WSHP-X2 Modules will always be

used. Each compressor will need to have a relay confi gured and wired
from these modules, and the VFD outputs will be wired from these
modules. The Suction Pressure Transducer for each compressor and the
Proof of Flow switch for each water circuit will also be wired into these
modules. See Figure 36 below and on page 45 for the wiring diagram.

On units confi gured for Half VFD/Half Fixed operation, the two VFD
Compressors will be driven from AOUT #1 & 3 on the 1st WSHP-X2
Module, although the individual compressor relays will be enabled
separately as needed. On units confi gured for Full VFD operation,
the 1st two VFD Compressors will be driven from AOUT #1 & #2 on
the 1st WSHP-X2 Module and the 2nd two VFD Compressors will be
driven from AOUT #1 & #3 on the 2nd WSHP-X2 Module. All four
compressor relays will be enabled separately as needed.

RNE 120 - 140 Ton Unit Compressor and Condenser Wiring

Connect To

RNE Controller

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. 2 ENABLE

COMP. 1 ENABLE

R1

R5

R3

COMM

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

HSSC Cable

GND

T1

WATER POF 1

BIN6

COM

E

LEAVING WATER
TEMPERATURE 1

T2

BIN7

WATER POF 2

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

SUCTION PRESSURE
TRANSDUCER 1

SUCTION PRESSURE
TRANSDUCER 2

AOUT1

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

Compressor 1

Compressor 2

COM

+

COM

+

LEAVING WATER
TEMPERATURE 2

Connect To

RNE Controller

WARNING!! Observe Polarity! All
boards must be wired with GND-to-
GND and 24 VAC-to-24 VAC.
Failure to observe polarity could
result in damage to the boards.

HSSC Cable

Connect To 2nd

WSHP-X2 Module

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

R5

COMM

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and 24
VAC-to-24 VAC. Failure
to observe polarity could
result in damage to the
boards.

HSSC Cable

GND

T1

WATER POF 1

BIN6

COM

E

LEAVING WATER
TEMPERATURE 1

T2

BIN7

WATER POF 2

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

SUCTION PRESSURE
TRANSDUCER 1

SUCTION PRESSURE
TRANSDUCER 2

AOUT1

AOUT3

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

Compressor 1

Compressor 2

COM

+

COM

+

LEAVING WATER
TEMPERATURE 2

AZ2-ALL-IOG-01F.indd